Electrical Installation 2 - 7
4185
300/350
R/L1, S/L2, T/L3,
,
1
M8
88.5
(10.0)
300 X 2P
(152 X 2P)
600Vac
UL Approved
vinyl-sheathed
or equivalent
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33
M8
88.5
(10.0)
300 X 2P
(152 X 2P)
3
M8
88.5
(10.0)
2/0
(67.4)
M16
867.4
(98.0)
3/0 X 2P
(85 X 2P)
r/
l
1,
s
200/
l
2
200,
s
400/
l
2
400
M4
12.4
(1.4)
14
(2.1)
4220
400/450
R/L1, S/L2, T/L3,
,
1
M8
88.5
(10.0)
500 X 2P
(253 X 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33
M8
88.5
(10.0)
400 X 2P
(203 X 2P)
3
M8
88.5
(10.0)
2/0
(67.4)
M16
867.4
(98.0)
250 X 2P
(127 X 2P)
r/
l
1,
s
200/
l
2
200,
s
400/
l
2
400
M4
12.4
(1.4)
14
(2.1)
4300
500+
R/L1, S/L2, T/L3,
,
1
M8
88.5
(10.0)
700 X 2P
(355 X 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33
M8
88.5
(10.0)
600 X 2P
(304 X 2P)
3
M8
88.5
(10.0)
2/0
(67.4)
M8
867.4
(98.0)
400 X 2P
(203 X 2P)
r/
l
1,
s
200/
l
2
200,
s
400/
l
2
400
M16
12.4
(1.4)
14
(2.1)
* Use 75
°
C copper wire or equivalent.
IMPORTANT
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
Line voltage drop (V) =
x wire resistance (
Ω
/km) x wire length (m) x current (A) x 10
-3
Table 2.2 480Vac Wire Sizes and Connector Specifications
Drive Model
CIMR-E7U
Nominal
Hp
Terminal Symbol
Terminal
Screws
Clamping
Torque
lb. in.
(N•m)
Recommended
Wire Size AWG
(mm
2
)
Wire Type
3
WARNING
Prior to removing any protective cover or wiring any part of the Drive, remove all power sources, including
main input power and control circuit power. Wait a minimum of 5 minutes after power removal, before
removing any cover. The charge lamp located within the Drive should be off prior to working inside. Even if
the charge lamp is off, one must measure the AC input, output, and DC Bus potential to insure safe levels
prior to resuming work. Failure to adhere to this warning may result in personal injury or death.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com