8 CC-Link Data Table
YASKAWA ELECTRIC
SIEP C730600 83D YASKAWA AC Drive Option SI-C3 Technical Manual
33
Note:
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency
Reference 2 flag) too often can shorten the performance life of the drive's internal memory.
Energy-Saving Unit Remote I/O
PLC
→
Energy-Saving Unit
Table 15 Remote I/O Table (PLC
→
Energy-Saving Unit)
Note:
Although RYF is triggered by the rising edge of the signal, they are otherwise enabled depending on the value that is input.
Device
<1> Terminals will differ depending on the model of the drive. Refer to
Terminals that Change depending on the Model of the Drive on page 37
for information on terminals.
Name
Description
Default
RY0
Run Command/Automatic
Run Command
ON: Run Command/Automatic Run Command,
OFF: Stop Command
–
RY1
Forced Run Command
ON: Forced Run Command,
OFF: Stop
–
RY2
Terminal S3 Function
Multi-Function Input: H1-03
H1-03 = 24: External
Fault
RY3
Terminal S4 Function
Multi-Function Input: H1-04
H1-04 = 14: Fault Reset
RY4
Terminal S5 Function
Multi-Function Input: H1-05
H1-05 = F: Through
Mode
RY5
Terminal S6 Function
Multi-Function Input: H1-06
H1-06 = F: Through
Mode
RY6
Terminal S7 Function
Multi-Function Input: H1-07
H1-07 = F: Through
Mode
RY7
Terminal S8 Function
Multi-Function Input: H1-08
H1-08 = 8: Baseblock
command (N.O.)
RY8
Reserved
–
–
RY9
External Baseblock
Command
ON: No converter output
–
RYA
External Fault
ON: External Fault Input (EF0)
–
RYB
Reserved
–
–
RYC
Monitor Reference
ON: Monitor data specified in the monitor code is set to remote register
RW
R0
.
When switching between
monitors using RYC
(Monitor Reference),
RYC needs to be turned
off and then back on
again after the monitor
code has been changed.
RYD, E
Reserved
–
–
RYF
Command Code Execute
Request
Request to execute the command code.
Triggered by the rising
edge of the signal.
RY10
Terminals M1-M2 Function
Multi-Function Relay Output 1 (terminal M1-M2)
–
RY11
Terminals P1-PC
Function
Multi-Function Photocoupler Output 1 (terminal P1-PC)
–
RY12
Terminals P2-PC
Function
Multi-Function Photocoupler Output 2 (terminal P2-PC)
–
RY13
Reserved
–
–
RY14
Terminal S1 Function
Multi-Function Input: H1-01
Function is disabled when
for the Run Command
(H1-01 = 4B).
RY15
Terminal S2 Function
Multi-Function Input: H1-02
Function is disabled when
for the Stop Command
(H1-02 = 4C).
RY16
RY17 Enabled/Disabled
Selection
–
–
RY17
Terminal MA/MB-MC
Function
Fault Contact Output (terminal MA/MB-MC)
–
RY18, 19
Reserved
–
–
RY1A
Fault Reset
Resets an energy-saving unit fault.
–
RY1B to 1F
Reserved
–
–