3.8 Main Circuit Wiring
68
YASKAWA ELECTRIC
SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual
■
Three-Phase 400 V Class
Table 3.3 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
2A0169
R/L1, S/L2, T/L3
70
50 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
70
50 to 95
–, +1
–
35 to 95
+3
–
50 to 95
35
25 to 35
M8
9 to 11
(79.7 to 97.4)
2A0211
R/L1, S/L2, T/L3
95
70 to 95
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
95
70 to 95
–, +1
–
35 to 95
+3
–
50 to 95
50
25 to 50
M8
9 to 11
(79.7 to 97.4)
2A0250
R/L1, S/L2, T/L3
95
×
2P
95 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
95
×
2P
95 to 150
–, +1
–
70 to 150
+3
–
35 to 150
M10
18 to 23
(159 to 204)
95
95 to 150
M12
32 to 40
(283 to 354)
2A0312
R/L1, S/L2, T/L3
95
×
2P
95 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
95
×
2P
95 to 150
–, +1
–
70 to 150
+3
–
70 to 150
M10
18 to 23
(159 to 204)
95
95 to 150
M12
32 to 40
(283 to 354)
2A0360
R/L1, S/L2, T/L3
240
95 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
240
95 to 300
–, +1
–
125 to 300
+3
–
70 to 300
M10
18 to 23
(159 to 204)
120
120 to 240
M12
32 to 40
(283 to 354)
2A0415
R/L1, S/L2, T/L3
120
×
2P
95 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300
95 to 300
–, +1
–
150 to 300
+3
–
70 to 300
M10
18 to 23
(159 to 204)
120
120 to 240
M12
32 to 40
(283 to 354)
Model
CIMR-A
Terminal
Recommended Gauge
mm
2
Applicable
Gauge
mm
2
Screw
Size
Tightening
Torque
N
x
m (lb.in.)
4A0002
4A0004
R/L1, S/L2, T/L3
2.5
2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
2.5 to 6
–, +1, +2
–
2.5 to 6
B1, B2
–
2.5 to 6
2.5
2.5 to 4
4A0005
4A0007
4A0009
R/L1, S/L2, T/L3
2.5
2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
2.5 to 6
–, +1, +2
–
2.5 to 6
B1, B2
–
2.5 to 6
2.5
2.5 to 6
4A0011
R/L1, S/L2, T/L3
2.5
2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
2.5 to 6
–, +1, +2
–
2.5 to 6
B1, B2
–
2.5 to 6
2.5
2.5 to 6
Model
CIMR-A
Terminal
Recommended Gauge
mm
2
Applicable
Gauge
mm
2
Screw
Size
Tightening
Torque
N
x
m (lb.in.)