5.2.5 Checklist for the EMC-compliant installation of controllers
EMC-measures
Space for Notes
Connection of the inactive parts
You should take special care to check the connections of:
n
Module racks
n
Frames
n
Screen and protected earth conductor
Are all the inactive metal parts interconnected by means of large-surface and low-
impedance connections?
Has a proper connection been installed with respect to the ground/protected earth con-
ductor system?
Has the isolation been removed from varnished and anodized surfaces or have these
connections been fitted with special contact washer?
Have the connection been protected from corrosion, e.g. by means of grease?
Have doors been grounded by means of grounding straps connected to the body of the
cubicle?
Cable routing
Cabling divided into groups?
Power cables (230 ... 400V) and signal lines installed in separate channels or
bunches?
Potential compensating
When installing the equipment at separate locations, check the installation of the
potential compensating line.
Cable screen
All covers of plugs are metallic?
All analog and data lines installed screened?
Line screens attached to the screening or the protected earth conductor?
Have the screens been connected by means of large-surface and low-impedance
cable clamps?
Cable screens grounded both-sided where possible?
Inductors
Have the coils of contactors controlled by means of contacts been connected to
snubber networks?
HMI
Industrial Security and Installation guidelines
Installation guidelines > Checklist for the EMC-compliant installation of controllers
HB160 | PPC | 67K-RRJ0 | en | 22-20
71
Summary of Contents for 67K-RRJ0
Page 1: ...PPC 67K RRJ0 Manual HB160 PPC 67K RRJ0 en 22 20 HMI Panel PC PPC010 EC ...
Page 14: ...HMI Hardware description Structure Interfaces HB160 PPC 67K RRJ0 en 22 20 14 ...
Page 58: ...4 7 Save and Exit HMI BIOS setup Save and Exit HB160 PPC 67K RRJ0 en 22 20 58 ...
Page 72: ...Appendix HMI Appendix HB160 PPC 67K RRJ0 en 22 20 72 ...
Page 73: ...Content A History of changes 74 HMI Appendix HB160 PPC 67K RRJ0 en 22 20 73 ...