For the cabling of the DC 24V power supply green plugs with CageClamp technology are
deployed. The spring-clip connector technology simplifies the wiring requirements for sig-
naling and power cables. In contrast to screw terminal connections, spring-clip wiring is
vibration proof.
Here also you can connect wires with a cross-section of 0.08mm
2
to 2.5mm
2
. You can
use flexible wires without end case as well as stiff wires.
Fix the conductors to the CageClamps like this:
1
Round opening for wires
2
Locking (orange) for screwdriver
3
Test point for 2mm test tip
The picture on the left side shows the cabling step by step from top view.
1.
For cabling you push the locking vertical to the inside with a suiting screwdriver and
hold the screwdriver in this position.
2.
Insert the insulation-stripped wire into the round opening. You can use wires with a
cross-section from 0.08mm
2
to 2.5mm
2
.
3.
By removing the screwdriver the wire is connected safely with the plug connector
via a spring.