Synergy Quick Start Guide
Ver: 20150709
Page 8 of 8
Backwash Schedule
The menus displayed for the backwash schedule depend on the option selected in menu B4,
as discussed in the Flush Timing section. Given that this default value is periodic, the
default scheduling values are as follows;
Default Values:
flush period of 2 hours, 1 period window from 00:00 to 23:59 and EoWF
disabled
For periodic flush timing, navigate to menu A6 to set the period at which backwashes will
operate. Backwashes will only run during configured period windows. Navigate to menu A7
to set how many period windows will be configured. Menu A8 is used to configure each of
the period windows by selecting a start and end time. Backwashes will run at the specified
period between these times. The first will start at the beginning of the window. Set the start
time to 00:00 and end time to 23:59 for 24 hour operation. Menu A9 allows the user to
enable or disable the end of window flush. When enabled, this option ensures that a flush
will run at the end of a period window.
For schedule flush timing, navigate to menu A10 and press select to choose the number of
backwashes to be configured on a given day. Navigate to menu A11 to configure each of
those backwash times individually but the setting the hours and minutes to start the
backwash at.
Backwash Days
Default Value:
All days enabled
Navigate to menu A12 for the Flush Days menu. Press select here to configure which days
backwashing will occur. All selected days here will follow the same schedule. The first set of
sub menus allows the user to enable all days or set custom days.