Starting the System
1. Ensure the power box switch on the
control panel is OFF.
2. Start the engine and set the engine
speed according to the electric
equipment you will use.
Note: See Engine Speed Versus Power
Output on page 40 for relationship
between engine speed and power output.
When tools or appliances that draw
heavy loads, such as a pump or air
conditioner, are started, the necessary
starting current required is greater than
the rated load. Set the engine speed at
2200 to 2500 rpm to handle the larger
draw.
3. Turn the power box ON / OFF switch to
ON. Ensure the Power Box is Running
indicator illuminates (Figure 1). When
lit, 230V are available and the system is
ready for use.
0004615
Inv
T
emp.
MORE SPEED
OVERLOAD
OFF
ON
Gen
T
emp.
Figure 1
Note: When restarting tools or appliances
that have a heavy draw, such as an air
conditioner, ensure the engine rpm is
sufficient to handle the additional load. See
General Specifications on page 39.
OPERATION
KMG65E Operation Manual
25