DC Inverter U-match Series Cassette Type Unit
18
2.2.1.2 Leveling
The water level test must be done after installing the indoor unit to make the
unit is horizontal, as shown below.
2.2.2 Outdoor Unit Installation
(1) If the outdoor unit is installed on a solid ground such as concrete, use M10
screw bolts and nuts to secure the unit and make sure the unit stands
erect and level.
(2) Do not install it on top of the building.
(3) If it vibrates and causes noise, please add rubber cushion between the
outdoor unit and the installation base.
(4) When the outdoor unit is in heating or defrosting, it needs to drain water.
When installing the drain pipe, plug the accompanied drainage connector
to the drainage hole on the chassis of the outdoor unit. Then connect a
drain hose to the drainage connector (If drainage connector is used, the
outdoor unit should be at least 10cm from the installation ground). See the
figures below.
(5) Plugs and drainage connector are not recommended if there is an
electrical heater on the chassis.