background image

 

 6 

AB-6474 

Dimensions (mm)   

1)  Dimensions of Neosensor main unit with Wall-direct mounting kit 

(Neosensor) 

(High Sensitivity Neosensor) 

 

(Surface view of mounting plate) 

Figure 1.  Dimensions (mm): Wall-direct mounting 

 

 

 

(77) 

(77) 

16.5 

38.5 

Wall-direct 
mounting kit 

90 
77 

77 

90 

(77) 

77 

90 

Wall-direct 
mounting kit 

45.5 

16.5 

77 

90 

(77) 

15 

15 

80 

Mounting screw 

(M3) 

φ

4.2

 

mounting hole 

Mounting 
hole 

66.7* 

80 

Note: 

When mounting the Neosensor, be sure to 
secure a longer than 15 mm clearance for 
wiring from the mounting surface inside the 

wall. 

Note: 

When mounting the Neosensor, be 
sure to secure a longer than 15 mm 
clearance for wiring from the 

mounting surface inside the wall. 

8.2 

4.2 

∗ 

Use JIS outlet box/box cover (JIS C8340 (1999)). 

Mounting dimension: 66.7 mm 

Mounting 
surface 

Mounting 
surface 

Summary of Contents for Neosensor HTY7043

Page 1: ...43 uses a Pt100 resistance thermometer sensor JIS C1604 Class A for a temperature sensing element and a polymer capacitive humidity sensor FP3 TM specially developed by Yamatake Corp for a humidity sensing element enhancing accuracy and reliability of temperature humidity sensing It is suitable for various applications such as commercial buildings or other indoor uses JIS Japanese Industrial Stand...

Page 2: ... out under the operating conditions specified in this manual to prevent equipment damages Always disconnect power source before performing any wiring to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Do not disassemble the product at any time except when removing the cover to install the product main unit Equipment damages may occ...

Page 3: ...efer to the table below Available model numbers HTY7043T1P00 With company logo HTY7043T1P00 1 Humidity 1 5 V DC Temperature Pt100 Neosensor Without company logo TY7043Z0P00 With company logo TY7043Z0P00 1 Temperature Pt100 Neosensor Without company logo TY7053Z0P00 With company logo TY7053Z0P00 1 Temperature Pt100 High Sensitivity Neosensor Without company logo TY7043Z0P01 With company logo TY7043...

Page 4: ...o 80 RH 15 C to 35 C Conditions 24 V DC input power supply 250 Ω resistive load 0 15 m s wind velocity and 60 minute warm up period Temperature Neosensor 4 5 minutes or less High Sensitivity Neosensor 2 5 minutes or less Reference values Time constant for wind velocity of 0 15 m s Humidity Neosensor 40 seconds or less Temperature Rated operating conditions Models HTY7043T and TY70X3Z series 0 C to...

Page 5: ...room control Models QY1100C QY1100D with rotary switch Thermoplate Model DY2000A1022 1 unit lengthwise mounting Model DY2000A1023 1 unit crosswise mounting Model DY2000A2023 2 unit crosswise mounting with outlet box Model DY2000A2024 2 unit crosswise mounting with switch box Model DY2000A3022 3 unit crosswise mounting Conduit connection type Thermoplate Model DY2000A1021 1 unit square mounting Mod...

Page 6: ...ounting kit 45 5 16 5 77 90 77 15 15 80 Mounting screw M3 φ4 2 mounting hole Mounting hole 66 7 80 Note When mounting the Neosensor be sure to secure a longer than 15 mm clearance for wiring from the mounting surface inside the wall Note When mounting the Neosensor be sure to secure a longer than 15 mm clearance for wiring from the mounting surface inside the wall 8 2 4 2 Use JIS outlet box box co...

Page 7: ...f Thermoplate mounting kit Figure 2 Dimensions mm Thermoplate mounting Note When mounting the Neostat be sure to secure a longer than 12 5 mm clearance for wiring from the mounting surface inside the wall 77 48 77 77 12 5 19 Thermoplate mounting kit 77 Mounting surface Note When mounting the Neostat be sure to secure a longer than 12 5 mm clearance for wiring from the mounting surface inside the w...

Page 8: ...lti Thermocase mounting Multi Thermocase mounting kit 85 23 72 8 52 Assembled dimension of device mounting plate of Multi Thermocase and Multi Thermocase mounting kit 66 7 mm 72 8 85 72 8 72 8 85 68 55 φ3 4 mounting hole 66 7 When multiple units of Neosensor and or Neostat are installed in a Multi Thermocase separate order required the Neosensor main unit covers are not used ...

Page 9: ...n a wall See Fig 4 1 Attach the mounting plate to the box cover outlet box mounting dimension 66 7 mm JIS C8340 1999 located inside the wall 2 Install the main part of the Wall direct mounting kit on the mounting plate See Fig 9 3 Connect the output lead wires of the Neosensor main unit to the external wires for the load side See Figs 15 and 16 4 Remove the cover from the Neosensor main unit and m...

Page 10: ...Wall direct mounting kit make sure to set the height adjusting levers on the left and right sides See Fig 12 to the upper position indicated by L 5 Reinstall the cover to the main unit to complete the installation procedure See Fig 8 Figure 5 Installation Neosensor with Wall direct mounting kit on conduit connection type Thermoplate 66 7 Accessory screws 4 flat head machine screws M3 16 External w...

Page 11: ...unit onto the Thermoplate mounting kit make sure to set the height adjusting levers on the left and right sides See Fig 12 to the upper position indicated by L 6 Place the cover back on the Neosensor main unit to complete the installation procedure See Fig 8 Figure 6 Installation Neosensor with Thermoplate mounting kit on Thermoplate Output lead wires Thermoplate mounting kit separate order requir...

Page 12: ...mocase be sure to set the height adjusting levers on the left and right sides of the Neosensor main unit to the lower position indicated by H Figure 7 Installation Neosensor in Multi Thermocase with Multi Thermocase mounting kit Note To mount the Neosensor main unit set the height adjusting lever on the left and right sides to the lower position before fixing the main unit on the Multi Thermocase ...

Page 13: ...ng kit Max 9 mm Figure 11 Pulling up the Neosensor main unit 3 Lower the height adjusting levers on the left and right The height adjusting levers are set to the upper position indicated by L for factory preset Figure 12 Height adjusting lever 4 Mount and fix the Neosensor main unit ont the main part of the Wall direct mounting kit with the 4 mounting screws Figure 13 Neosensor mounting on the Wal...

Page 14: ...ng Always check wiring before supplying power Never share 24 V AC transformer with any other product Figure 17 Wiring diagram Black lines for power supply and for humidity output are connected inside the Neosensor Model HY7043T1000 Model TY7043Z0P00 Model TY7053Z0P00 Pt100 Brown Black Blue Black Red White White A B B 24 V AC 24 V DC 1 5 V DC J1 1 A 2 B 3 A 4 B 5 NC 6 B 7 NC 8 B Model TY7043Z0P01 M...

Page 15: ...ontroller with a low pass filter removal ratio of 40dB or higher in normal mode for receiving signals Connect an isolator for the controller input circuit if a removal ratio is not enough No problem will occur for connecting with a Yamatake s controller DC power supply can be shared Though loop is formed at common common mode noise affects a little Correct 24 V DC Temperature humidity sensor Tempe...

Page 16: ...m humidity single point calibration Replace the sensor 3 Humidity single point calibration Models HTY7043T HY7043T When you find an output error of the humidity sensor the sensor can be calibrated with the adjustment knobs VR1 for rough adjustment VR2 for fine adjustment located inside the humidity sensor The output value is increased by turning these knobs clockwise and decreased by turning them ...