Installation procedure: Neosensor on conduit connection type Thermoplate (See Fig. 5.)
1) Attach the mounting plate to the conduit connection type Thermoplate.
2) Install the main part of Wall-direct mounting kit on the mounting plate. (See Fig. 9.)
3) Connect the output lead wires of the Neosensor main unit to the external wires (for the load side). (See Figs. 15 and 16.)
4) Remove the cover from the Neosensor main unit, and mount the main unit on the Wall-direct mounting kit with the 4
main-unit accessory screws (M3
×
16). When mounting the main unit onto the Wall-direct mounting kit, make sure to set
the height-adjusting levers on the left and right sides (See Fig. 12.) to the upper position (indicated by "L").
5) Reinstall the cover to the main unit to complete the installation procedure. (See Fig. 8)
Figure 5. Installation: Neosensor with Wall-direct mounting kit (on conduit connection type Thermoplate)
66.7
㎜
Accessory screws
(4 flat-head machine
screws, M3
×
16)
External wires
(for the load side)
Wall-direct mounting kit
(separate order required)
Wire-pipe connection
(open-wiring) type
Thermoplate
(separate order required)
Neosensor
Main unit of Neosensor
Cover
Accessory screws
(2 pan-head machine screws, M4
×
8)
Accessory screws
(1 flat-head machine screw,
M3
×
16)
Mounting plate
Main part of Wall-direct mounting kit
Output lead wires