PRODUCT DATA
® U.S. Registered Trademark
Copyright © 1997 Honeywell Inc. • All Rights Reserved
65-0203
7800 SERIES
EC7885A/RM7885A Relay Module
APPLICATION
The Yamatake Honeywell EC7885/RM7885 is a microprocessor based
integrated burner control for semi-automatically fired gas, oil or
combination fuel single burner industrial applications. The 7885A
requires a Relay Module Subbase and Amplifier to complete the
system. Options include Keyboard Display Module, Personal Computer
Interface, DATA CONTROLBUS MODULE™, Remote Display Module
and COMBUSTION SYSTEM MANAGER™ Software.
The 7885A is programmed to provide a level of safety, functional capability
and features beyond the capacity of conventional controls.
The 7885A is adaptable to continuous firing, high-low or modulating
firing rate for semi-automatic burner sequencing. Functions
provided by the 7885 include flame supervision, system status
indication, system or self-diagnostics and troubleshooting.
The 7885A operates with any of the following types of ignitions:
1. Torch-ignited main burner using the S445A Start-Stop Station,
or any conventional knee- or foot-operated start-stop station.
2. Torch-ignited pilot using the S445A Start-Stop Station, or any
conventional knee- or foot-operated start-stop station.
3. Direct-ignition oil burner or electrically ignited pilot, using the
S445A Start-Stop Station, which maintains electric ignition as
long as the Start Switch is depressed (up to 15 minutes).
FEATURES
•
Safety features:
—
Closed loop logic test.
—
Dynamic AMPLI-CHECK®.
—
Dynamic input check.
—
Dynamic safety relay test.
—
Dynamic self-check logic.
—
Expanded safe-start check.
—
Internal hardware status monitoring.
—
Tamper resistant timing and logic.
•
Lockout if Start Switch is held 15 minutes.
•
Access for external electrical voltage checks.
•
Application flexibility.
•
Communication interface capability.
•
Dependable, long-term operation provided by microcomputer
technology.
•
First-out annunciation and system diagnostics are provided by
an optional 2 row by 20 column Vacuum Fluorescent Display
(VFD) located on the optional Keyboard Display Module.
•
Five LEDs for sequence information.
•
Interchangeable plug-in flame amplifiers.
•
Local or remote annunciation of 7885A operation and fault
information (optional).
•
Nonvolatile memory; 7885A retains history files and
sequencing status after loss of power.
•
Remote reset (optional).
•
Report generation (optional).
•
Shutter drive output.
•
Burner controller data (optional):
—
Flame signal strength.
—
Hold status.
—
Lockout/alarm status.
—
Sequence status.
—
Sequence time.
—
Total hours of operation.
—
Total cycles of operation.
—
Fault history providing the six most recent faults:
–
Cycles of operation at the time of the fault.
–
Fault message and code.
–
Hours of operation at the time of the fault.
–
Sequence status at the time of the fault.
–
Sequence time at the time of the fault.
—
Diagnostic information:
–
Device type.
–
Flame amplifier type.
–
Flame failure response time.
–
Manufacturing code.
–
On/off status of all digital inputs and outputs.
–
Software revision and release of 7885A and optional
Keyboard Display Module.
Contents
Specifications ......................................................................
Ordering Informationn .........................................................
Principal Technical Features ...............................................
Safety Provisions ................................................................
Installation ........................................................................... 9
Assembly ............................................................................. 16
Operation ............................................................................ 19
Checkout ............................................................................. 21
Troubleshooting .................................................................. 28