3. Protection of contact of switch

・ Contact protection circuit is used to extend the service life of contact. It reduces generation of noise at 

the time of switching on and off. It also minimizes carbide and nitric acid gas generated by arc. Use this 
circuit correctly, otherwise it will cause reverse effect, making the matter worse.

・ In  case  of  using  contact  protection  circuit,  pay  attention  the  operating  time  is  possibility  of  delaying  a 

little. The following are typical examples of contact protection circuit.

a) Typical example of protective circuit

Example of circuit

Power supply

Special remarks for application and selection

DC

AC

Varistor
method

This  method  is  intended  not  to  apply  voltage  beyond 
limit of varistor to inbetween contacts. It delays a little 
time to return inductive load such as relay.
Select  the  most  conformed  rated  model  in  terms  of 
power  supply  voltage  and  load  capacity  in  selected 
article by varistor maker.

C・R
method

It  delays  a  little  time  to  activate  or  return  inductive 
load such as relay.
As for CR value, to contact current and contact voltage, 
the estimate value is C : 0.5 μ F / A, R : 1.0 Ω / V.
However,  it  differs  according  to  the  characteristics 
of  load,  therefore,  be  sure  to  confirm  to  select  by 
experiment.

Diode
method

×

This  method  is  intended  to  consume  counter 
electromotive  force  of  inductive  load  by  diode 
and  avoid  to  apply  high  voltage  to  inbetween  the 
contacts.
This method makes the return time of inductive load 
slower.Choose  the  diode  rated  current  is  more  than 
load current and counter withstand voltage more than 
10 times of power supply voltage.

Diode +
Zener diode
method

×

Diode method proves to be effective when the return 
time takes too long for inductive load such as relay. 
When  you  choose  zener  voltage  of  zener  diode, 
choose base on power supply voltage. Be careful with 
limitations  having  this  method.  Because  load  is  too 
big, larger capacity zener diode is needed for reverse 
surge power.

P.S. : Power supply,  I.L. : Inductive load

b) Example of wrong protection circuit

Condenser method

This  is  very  effective  to  remove  arc  at  the  time  of 
off-contact,  but  this  is  likely  to  run  charged  current 
to  condenser  leading  to  contact  sticking  and  short 
service life at the time on-contact.

This is very effective to remove arc at the time of off-
contact, but this is likely to run short circuit current 
accumulated  in  the  condenser  leading  to  contact 
sticking on contacting.
This  is  likely  to  short  service  life  at  the  time  on-
contact.

P.S. : Power supply,  I.L. : Inductive load

If the load is larger than the specifi ed contact capacity, use a secondary relay. In general, the load voltage and 
the corrent is too less to the life of contact is longer. However, this does not expect for a low electirical load. 
Manostar switches cannot directly shut off the circuit of 250 V AC or more.

ᵧᵌᵪᵌ

ᵮᵌᵱᵌ

ᵧᵌᵪᵌ

ᵮᵌᵱᵌ

ᵧᵌᵪᵌ

ᵮᵌᵱᵌ

ᵧᵌᵪᵌ

ᵮᵌᵱᵌ

ᵮᵌᵱᵌ

ᵧᵌᵪᵌ

ᵧᵌᵪᵌ

ᵮᵌᵱᵌ

Summary of Contents for MS65F

Page 1: ...I N S T R U C T I O N M A N U A L 653 0031 1 Nishi shiriike cho Nagata ku Kobe Japan TEL 078 631 6000 FAX 078 631 6020 READ THE INSTRUCTION MANUAL RoHS Compliant...

Page 2: ...Caution of piping 6 7 Installation position 6 SETTING OF PRESSURE 1 Switch contact con guration 7 2 Setting of upper limit lower limit 7 3 Reset time 8 ABOUT BUILT IN MICRO SWITCH 1 Material of conta...

Page 3: ...instrument The instrument is measurable for air and non corrosive gas only The machine is exclusive use of dry air 90 RH or less Using measuring the water or oil it may be damaged and causes the accid...

Page 4: ...ce pressures Materials of pressure receiving element Pa kPa 60D 10 60 0 01 0 06 2 0 Pa 15 0 Pa Polyester lm 120D 20 120 0 02 0 12 4 0 Pa 20 0 Pa 300D 50 300 0 05 0 3 8 0 Pa 40 0 Pa 600D 100 600 0 1 0...

Page 5: ...de 10 10 to 50 Hz Acceleration 39 m s2 each two hours on triaxial directions 100 m s2 each six times on triaxial direction Between each terminal and case 20 M or more 500 V DC megger Between each term...

Page 6: ...trical load type The general electrical load type is decreased contact reliability refer to p 8 The withstanding pressure of the pressure receiving element means The max pressure under which the diaph...

Page 7: ...nt of negative pressure Connect the tube to the low pressure side piping connector blue or L The high pressure port red or H should be opened to atmosphere but do not remove the piping connector c Mea...

Page 8: ...it once in a while After the cleaning of the tank check that the air tightness is fully kept c Measurement of high temperature gases In the pressure measurement of high temperature gas use the pressur...

Page 9: ...pressure the other is called lower limit setting type type L which is adjusted on reset pressure Be careful about the difference between the upper and lower limit setting switched and also understand...

Page 10: ...contact for low electrical load cross point contact Magni ed drowing of contact for general load small rivet contact point 2 Contact material and applicable mecanism for low voltage and low current c...

Page 11: ...ive force of inductive load by diode and avoid to apply high voltage to inbetween the contacts This method makes the return time of inductive load slower Choose the diode rated current is more than lo...

Page 12: ...acid and it may also cause electrical contact failure or malfunction of switches b Silicone gas If the gas to be measured contains silicon produced from silicon contained in oil grease filling agent...

Page 13: ...ain to x Replacement of air lter In case of using model with air lter MS65F depending on amount of work conduct disassembly and clean out once in 2 years periodically and replace lters and packings wi...

Page 14: ...rument life For vinyl or plastic tube For metal tube Product code FG VT6 S Product code FG MT6 S T joint For vinyl or plastic tube Product code TVT6 4 6 For branching different I D 6 and 4 Product cod...

Page 15: ...og speci cations or manual Handling or usage of the product other than as described in our product catalog speci cations or manual 2 Breakdown due to a reason other than a fault within our product 3 A...

Reviews: