5-49
ELEC
GENERATOR SYSTEM
11. Rotor remagnetization
9
Disconnect the exciter field coil coupler
(Black–White) at the end of the genera-
tor unit.
9
Start the engine (with no load).
9
Connect the DC 12 V battery to the sta-
tor side of the exciter field coil coupler,
battery
-
to coupler terminal (Black),
and battery
+
to coupler terminal
(White), for 2–5 seconds.
9
Remove the battery and reconnect the
exciter field coil coupler.
9
Recheck the main coil AC output voltage.
OUT OF
SPECIFICATION
Proceed to step 12.
MEETS
SPECIFICATION
No further action necessary.
NOTICE
Do not connect the battery for more than a
few seconds. This may deteriorate the bat-
tery.