Delayed Egress
Installation Instructions
7100, 7200 Series Exit Device
80-9470-0162-000 10/20
17
Wiring Diagram - “O” Trim Monitor Entry with External Door Position Switch
* Door Position Switch (DPS) made by other manufacturers.
Operation:
Door Position Switch (DPS)* is used to activate alarm when door has been forced open. It also
prevents device from being armed when door is propped open.
“O” trim monitor switch, when activated, will bypass unit and allow entry. Unit must be manually
reset for rearming with cylinder key. (Figure 12)
NOTE: Requires “O” trim monitor switch on device for alarm shunting.
Figure 11
Figure 12
18
Wiring Diagram - 690F Electric Trim Control
Operation:
Fail Safe Trim allows normal access control for entry, and also allows entry during power failure or
fire alarm activation. (Figure 11)
Electric trim operation will not affect armed device.