Heat / Cooling meter integrator PolluTherm 
Installation and operation instructions 
 

 

M H 6111 INT PolluTherm, page 1 

The integrator PolluTherm is used for energy 
consumption measurement in heating or cooling 
systems filled with the energy carrier liquid water. 
PolluTherm may also be used with water 
containing antifreeze using a programmed 
correction factor. In this case the PolluTherm is 
not officially metrologically calibrated. These 
installation and operation instructions specify how 
to install and operate the integrator PolluTherm. 
They are an essential part of the supplied items 
and shall be handed over to the final user. 
 

Content 

 
Supplied items ..................................................... 1

 

1. Technical data ................................................. 1

 

2. Safety instructions ........................................... 2

 

3. Required tools .................................................. 2

 

4. Combination of the sub-units ........................... 2

 

4.1 Programming the input pulse value ............ 2

 

5. Installation of the sub-units .............................. 3

 

5.1 Flow sensor ................................................ 3

 

5.3 Mounting of the integrator ........................... 4

 

6. Connection of the sub-units ............................. 4

 

6.1 Connection of the flow sensor .................... 5

 

6.2 Connection of the temperature sensors ...... 5

 

7. Exchange of the integrator module .................. 5

 

8. Display options ................................................ 6

 

8.1 User menu (example) ................................. 6

 

8.2 Target day menu (example) ....................... 7

 

8.3 Archive menu (example)............................. 7

 

8.4. Service menu (example) ............................ 8

 

8.5 Control menu for tariff purposes (example) 9

 

8.6 Parameter menu (example) ........................ 9

 

9. Functional test, sealing .................................. 10

 

10. Potential error situations .............................. 10

 

11. Data interface and options ........................... 10

 

11.1 Optical interface ..................................... 10

 

11.2 M-Bus-plug-in unit acc. to EN 13757-3 ... 10

 

11.3 Remote reading plug-in unit ................... 11

 

11.4 M-Bus plug-in unit with two contact inputs
 ....................................................................... 11

 

11.5 USB plug-in unit (for M-Bus slot) ............ 11

 

11.6 LONWORKS

®

-FTT10A (for M-Bus slot) . 11

 

11.7 Inserting the plug-in unit into the heat 
meter .............................................................. 11

 

11.8 Combined heating/cooling meter (ordering 
option) ............................................................ 11

 

11.9 Optional integrated data logger (ordering 
option) ............................................................ 12

 

11.10 Retrofitting from battery unit to power 
supply unit ...................................................... 12

 

12. Information on the extension of temperature 
sensor cables ..................................................... 12

 

Annex 1: Declaration of conformity acc. directive 
2004/22EC (MID) ............................................... 14

 

  

 

Supplied items 

 

  Integrator PolluTherm (incl. temperature 

sensors and immersion sleeves, where 
appropriate) 

 

Sealing material (self-lock seals, sealing 
wire), cable binders for strain relief 

 

  Fastening material (2 screws, 

2 dowels, C-rail) 

 

  These installation and operating instructions 

 
 

1. Technical data 

 

Integrator 

Temperature measuring 
range 

  

 = 1 … 180 °C 

Temperature difference 
range 

 = 3 … 150 K 

Switch-off threshold 

0,15 K 

Measuring accuracy 

Better than (%): 
+ (0,5 + 

min

 / 

Updating time and 
integration  cycles resp.: 
 
- Temperatures 
- Flow rate, power 
- Energy, volume 
 

 
 
 
2 sec 
4 sec 
4 sec (16 sec *) 
* in case of battery supply 

Optical data interface 

Physical acc. to EN 61107 
Data record acc. to EN 13757-3 

Suitable temperature  
sensors 

Pt 500 
Connection in two- or four-wire 
technology 

Power supply 
(certification period of the 
meter may be defined by 
national laws) 

Battery for 6 years 
(optional: 11 years) 
or mains supply 230 V AC or 
24 V AC 

Electromagnetic 
environment condition 

Class E 1 

Mechanical environment 
condition 

Class M 2 

Protection class 

IP 54 

Ambient temperature 

5 … 55 °C 

Storing temperature 

-20 … +65 °C 

Relative air humidity 

< 93 % 

Size (H x B x T) 
in terms of wall mounting 

ca. 159 x 125 x 52 mm 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Pulse input value 

in l 

0,25 

or 

2,5 

or 

10 

25 

or 

100 

250, 

1.000 or 

10.000 

Display of the 

integrator with 

decimal digits for 

m³, MWh or GJ 

00000,000 000000,00 0000000,0  00000000 

Pulse value in case 

of remote heat 

quantity reading in 

MWh or GJ 

0,001 0,01  0,1 

Pulse value in case 

of remote volume 

reading in l 

1 10 

100 

1.000 

 

Summary of Contents for SENSUS PolluTherm Integrator

Page 1: ...t into the heat meter 11 11 8 Combined heating cooling meter ordering option 11 11 9 Optional integrated data logger ordering option 12 11 10 Retrofitting from battery unit to power supply unit 12 12...

Page 2: ...tection Only specially trained and authorized personnel are permitted to carry out the connection Moreover attention is to be paid to the national technical rules Voltage 220 240 V AC or 24 V AC Frequ...

Page 3: ...g systems It is recommended to install the flow sensor in the warmer line return pipe of the cooling device PolluTherm X installation in warmer line has to be used Please note the approved minimum tem...

Page 4: ...of the pipe diameter Refer to the following guide for installing such temperature sensors Nominal sizes DN 50 Install the temperature sensors in an angle of 45 towards the flow direction see figure 4...

Page 5: ...8 Four wire connection 7 8 und 3 4 Screening if any Start by removing the appropriate preshaped rubber part from the integrator housing see figure 7 Then pull the cable through the hole in the presha...

Page 6: ...ntervals of 4 seconds and shows the accumulated heat energy By a push on the red key the first display item in the user menu accumulated heat energy is activated The other five menus can be obtained b...

Page 7: ...es on an adjustable annual target Target day value for heat and cooling energy resp Target day value for volume Target day value for tariff 1 if activated Target day value for tariff cold if activated...

Page 8: ...play shows a month selectionor wait for five minutes 8 4 Service menu example Each display item is marked with a man symbol The service menu shows maximum values and meter settings Absolute maximum fl...

Page 9: ...t three digits of the eight digit serial number on the meter housing At the beginning 000 appears Push the key for approx 2 seconds the zero on the left side starts flashing By continuously pushing th...

Page 10: ...ow temperature sensors In most cases the error situation Err 1010 is caused by temporary system conditions where the temperature in the warmer line drops by at least 3K below the temperature in the co...

Page 11: ...r reading 0 00 m The activation of the inputs has to be done via the service software MiniCom menu item set pulse input parameters The meter IDs of the pulse meters have to be set there as well as the...

Page 12: ...only the screw on the right side under the KK1 seal user seal of the plastic cover Pull the integrated module forward from the connection The seals in the middle and on the left side may not be remove...

Page 13: ...the lower 3 and 4 the electric resistance of the extension cable or cables does do not influence the measurement and the reading of the temperatures Material number 28505033 Edition 007 August 2019 Su...

Page 14: ...Heat Cooling meter integrator PolluTherm Installation and operational instructions M H 6111 INT PolluTherm page 14 Annex 1 Declaration of conformity acc directive 2004 22EC MID...

Reviews: