HONEYWELL LWCO
120 VOLT
UNI-MATCH
WATER FEEDER
MODEL
WF2-U-120
L1
A
B
L2
A
B
W N H
• Connect wire from terminal 'N' of water feeder
to terminal 'L2' on LWCO.
• Connect wire from terminal 'H' of water feeder
to terminal 'L1' on LWCO.
• Connect jumper wire from terminal 'L1' to
terminal 'A' on the low water cut-off.
• Connect wire from terminal 'W' of water feeder
to terminal 'A' on LWCO.
Diagram 16 WF2-U-120 / Honeywell LWCO (120 volt)
NC COM NO L N GND P
W N H
TACO LWCO
120 VOLT
Field or
Factory
Installed
Jumper
Wire
UNI-MATCH
WATER FEEDER
MODEL
WF-U-120
• Connect wire from terminal 'N' of water feeder
to terminal 'N' on LWCO.
• Connect wire from terminal 'H' of water feeder
to terminal 'L' on LWCO.
• Connect wire from terminal 'W' of water feeder
to terminal 'NO' on LWCO.
Diagram 17 WF2-U-120 / TACO LWCO (120 volt)
UNI-MATCH
WATER FEEDER
MODEL
WF-U-24
NC COM NO L N GND P
W N H
TACO LWCO
24 VOLT
Field or
Factory
Installed
Jumper
Wire
• Connect wire from terminal 'N' of water feeder
to terminal 'N' on LWCO.
• Connect wire from terminal 'H' of water feeder
to terminal 'L' on LWCO.
• Connect wire from terminal 'W' of water feeder
to terminal 'NO' on LWCO.
Diagram 18 WF2-U-24 / TACO LWCO (24 volt)