BURNER

101A

120 VAC
SUPPLY

N

H

24V

1

2

3

4

69

Wiring Alternatives - Controls of Different Voltages

For 120V Burner/24V Feeder setups

For 24V Burner/120V Feeder setups

BURNER

101A-24

120 VAC
SUPPLY

24V TRANSFORMER
(101-24V-48)

TO AVOID DAMAGE TO 101A
SOLENOID COIL, TRANSFORMER
101-24V-48 MUST BE USED.

N

H

1

2

3

4

69

Wire only terminals 1 and 2 into the millivolt circuit. Do not
attach any other wiring to terminals 1 and 2.

Install wire (A) from water feeder to 120 volt Neutral wire.

Install wire (B) from water feeder to terminal 4 of the low
water cut-off.

Install wire (C) from terminal 3 of the low water cut-off to 120
volt Hot wire.

MILLIVOLT

BURNER

CIRCUIT

1

2

3

4

101A

 FEEDER

A

B

C

120 VAC
SUPPLY

HOT

NEUTRAL

WIRE

NUTS

Models 69-MV-P and 369-MV Millivolt Burner Circuit Controls with Water Feeder
Millivolt Burner Control and Model 101-A 120V Water Feeder

24V TRANSFORMER

(101-24V-48)

1

2

3

4

101A-24

A

C

D

B

E

120 VAC 

SUPPLY

WIRE

NUTS

MILLIVOLT

BURNER

CIRCUIT

Wire only terminals 1 and 2 into the millivolt circuit.
Do not attach any other wiring to terminals 1 and 2.

Install wire (A) from 120 volt circuit Neutral wire 
to the transformer input Neutral terminal.

Install wire (B) from burner circuit Hot wire to the
transformer input Hot terminal.

Install wire (C) from transformer output Neutral 
terminal to the water feeder.

Install wire (D) from the water feeder to terminal 4 
on the low water cut-off.

Install wire (E) from terminal 3 on the low water 
cut-off to the transformer output Hot terminal.

Millivolt Burner Control and Model 101-A 24V Water Feeder

To prevent damage to the water feeder, a McDonnell
& Miller transformer Model 101-24V-48 must be used.

!

IMPORTANT

To prevent damage to the water feeder, a McDonnell
& Miller transformer Model 101-24V-48 must be used.

!

IMPORTANT

5

Summary of Contents for McDonnell & Miller 69 Series

Page 1: ...series with the burner control circuit to provide safety redundancy protection should the boiler experience a low water condition Moreover at each annual outage the low water cut offs should be disma...

Page 2: ...D AS PILOT SWITCH IN SERIES WITH HOLDING COIL OF AUTOMATIC STARTER NEUTRAL WIRE TO TWO WIRES OF 101A OR TO ALARM CIRCUIT HOT WIRE TO BURNER JUMPER SAFETY SWITCH 02 04 10 30 USED WITH MODEL 101 ELECTRI...

Page 3: ...ete the installation by securing the control onto the barrel by tightening the eight 8 clamping ring screws to 5 ft lbs 7 N m torque TOP on the switch terminal panel MUST be in the up position INSTALL...

Page 4: ...th M M Model 101 A Electronic Water Feeders 120V Burner and 120V Feeder BURNER 120 VAC SUPPLY 1 2 3 4 N H 101A 69 Using a wire nut connect a wire from the neutral side of the power sup ply to one of t...

Page 5: ...ater Feeder Millivolt Burner Control and Model 101 A 120V Water Feeder 24V TRANSFORMER 101 24V 48 1 2 3 4 101A 24 A C D B E 120 VAC SUPPLY WIRE NUTS MILLIVOLT BURNER CIRCUIT Wire only terminals 1 and...

Page 6: ...seconds seconds 3 100 100 One seconds seconds 2 3 M M M M 2 3 Wiring Diagrams continued Series 69 Low Water Cut off with M M Model WF 2 U Electronic Water Feeders The Uni Match water feeders have a t...

Page 7: ...9...

Page 8: ...poses Seller warrants the goods purchased hereunder with the exception of membranes seals gaskets elastomer materials coatings and other wear parts or consumables all of which are not warranted except...

Reviews: