Xylem McDonnell & Miller 63 Series Instruction Manual Download Page 6

6

TROUBLESHOOTING

TESTING

Problem:

1. Burner does not shut off on low water.

a.

Cause:

Float chamber is loaded with mud or
sediment.

Test:

With water level below the control
check if terminals C and N.C. are open.
If not, remove switch and manually test
if terminals C and N.C. can be opened.

Solution:

Open float chamber and clean. At this
time, check for a build-up of scale or
sediment between corrugations of the
bellows.

b.

Cause:

Contacts are fused together.

Test:

Remove switch and operate manually to
verify proper switch operation.

Solution:

Replace switch. Check electrical load
and make sure it is within the ratings
of the switch.

CUT  OFF

LEVEL

TEST
OPENING

• Control can be tested on a hot water 

boiler by gently inserting a screwdriver 
or similar tool in the test opening below 
the switch (see drawing) and lifting linkage 
to cause float to drop, thereby simulating a 
low water condition.

Summary of Contents for McDonnell & Miller 63 Series

Page 1: ...INSTRUCTION MANUAL MM 206H 246746...

Page 2: ...the diagram that represents your boiler c Crosses should be used at each right angle connection for inspection and cleaning d Make sure the blow down valves are full port e While the burner is operati...

Page 3: ...riser going to the radiation or to the compression tank IMPORTANT The horizontal equalizing pipe should be below the horizontal run going to the radiation If it is not an air pocket will be created a...

Page 4: ...te the installation as described in the low water cut off installation instructions 6 After all piping assembly has been completed refill the system with water turn on all electrical supply and bring...

Page 5: ...N C C N O N C C Neutral 120 V A C Supply Hot Low Water Alarm Burner Circuit Line Load SCHEMATIC OF SWITCH OPERATION Water Level Normal Burner On Alarm Off Low Water Alarm Terminals Low Water Cut Off T...

Page 6: ...k for a build up of scale or sediment between corrugations of the bellows b Cause Contacts are fused together Test Remove switch and operate manually to verify proper switch operation Solution Replace...

Page 7: ...es no longer operate properly If you choose to replace the switch es order the proper McDonnell Miller replacement switch or switch assembly and follow the Repair Procedure provided More frequent blo...

Page 8: ...ngs and other wear parts or consumables all of which are not warranted except as otherwise provided in the quotation or sales form will be free from defects in material and workmanship for a period of...

Reviews: