Parameters of the Secondary Menu
Before entering the secondary menu these instructions must be read
carefully to prevent incorrect settings which will cause malfunction.
All parameters can also be set during operation. Therefore you should be trained how to
use the secondary menu.
We suggest stopping the HYDROVAR by pressing
Ð
OFF during the first start-up.
INVERTER STOP
ON -> START
Press
¾
for 3 seconds to change to
PASSWORD
0000
Set Password (0066 = Default) by pressing
Ï
or
Ð
NOTICE: The password must be entered at each entry into the submenu
PASSWORD
0066
Confirm by pressing
¾
and the first window of the sub
menu is shown
J O G – MODE
0.0Hz X.XX Bar
In the following chapters all available parameters of the secondary menu are listed
(on the index window there is shown the European default setting).
9.1
JOG-MODE
J O G – MODE
0.0Hz X.XX Bar
Both Actual output frequency and actual value are
shown.
•
By pressing
Ï
or
Ð
in this menu, the internal controller of the HYDROVAR will be shut off
and the inverter changes to manual mode.
•
With the buttons
Ï
and
Ð
you can set any constant speed, with no influence of the actual
value of the control signal!
•
If this value becomes 0 Hz the HYDROVAR stop.
•
If you set a frequency above 0.0 Hz, the HYDROVAR will start operating normally again in
automatic mode as soon as you change window.
Press the
¾
button to change to the next parameter