INSTALLATION

An equalizing line is recommended for continuous
operation applications as with water storage tanks.
See Figure 1.
The Hoffman No. 792 Water Vent should always 
be installed with a safety drain from the discharge
port to a suitable waste. At high rates of discharge
at pressure, a fine mist will be discharged with the
air. If dirt lodges between valve pin and seat, the
valve will not close properly and water will be 
discharged at system pressure until problem is
corrected.

Model 792 Capacity

Water Pressure

Air Discharge to Atmosphere

psig (bar)

CFM (M

3

/min.)

100

(6.9)

10

(.28)

150

(10.3)

15

(.42)

200

(13.8)

20

(.57)

250

(17.3)

25

(.70)

Temperature and Pressure Limits
Maximum Temperature: 
300˚F (149˚C)
Maximum Operating Pressure: 250 psig (17.3 bar)
Maximum Hydrostatic Pressure: 350 psig (24.2 bar)

1/2’’ EQUALIZING LINE WHERE

LARGE AMOUNTS OF AIR

MUST BE VENTED

1/2’’ SAFETY

DRAIN

1’’ MINIMUM

STORAGE TANK

INSTALL SHUTOFF VALVES

IN VERTICAL PIPE ONLY

FIGURE 1

1/2’’ SAFETY

DRAIN

HIGH POINT OF SYSTEM

FIGURE 2 

INSTALL SHUTOFF VALVES

IN VERTICAL PIPE ONLY

Note: Leave shut-off valves open
for proper installation. Close only
to service unit.

NOTE

The air vent will discharge air and possibly some liquid

during its normal functioning. Avoid eye, face or skin

contact with top area of air vent. We recommend the vent

connection be piped to a drain to prevent accidental con-

tact with discharging fluids. Failure to follow this instruc-

tion can result in serious personal injury and/or property

damage.

!

WARNING

Corrosion or leakage are indications that the air vent may

be about to cause serious damage from leakage or rup-

ture. It should be periodically inspected and if noted, air

vent must be replaced or serviced. Failure to follow this

instruction can result in serious personal injury and/or

property damage.

!

WARNING

System fluid under pressure and/or at high temperatures

can be very hazardous. Before servicing, reduce system

pressure to zero or isolate the air vent from the system.

Allow system to cool below 100˚F. Failure to follow this

instruction can result in serious personal injury and/or

property damage.

!

WARNING

Model 792
High Pressure Water
Vent Valve (complete unit) . . . . . . . . . . . . 401494
Service Parts Available
Cover Gasket Part No.. . . . . . . . . . . . . . . . . 601273
Internal Parts Kit Part No. . . . . . . . . . . . . . . 600204
(includes cover gasket, pin, seat, lever arm, yoke,
cotter pin and integral connecting hardware)
Float . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600247