NOTICE:
– In AUTOMATIC mode, the pump runs if the pressure of the system is below the
Pressure Drop (
dP
) value.
–
If necessary, press (2)
to set MANUAL mode and turn off the pump.
5.2.1 Operating parameters
Refer to
on page 16 for an explanation of the buttons on the user
interface.
In AUTOMATIC mode, press (4)
or (5)
to change the Operating Parameter
being displayed.
Table 2: Operating parameters
Parameter
Description
Unit
Range
P
System pressure
PSI
0.0–99
Fr
Motor Frequency
Hz
Min–60
A
Output Current
Ampere
0–In
3
°C
Temperature of the power
module
Degrees Celsius (°C)
0–80
The last parameter to be selected is shown continuously on the display.
5.2.2 Counter and Alarm Log Menu
Refer to
on page 16 for an explanation of the buttons on the user
interface.
In MANUAL Mode, in addition to the parameters indicated in
page 18, it is possible to view the Counter and Alarm Log.
To access this menu, press and hold (3)
and (5)
at the same time for three
seconds.
Press (6)
to select the next parameter. The parameters will be displayed in the
sequence shown in the following table. The menu will exit after the
A9
parameter or press
(3)
to exit the menu.
Table 3: Counter and Alarm Log Menu Parameters
Parameter
Description
HF
Number of hours the controller has been powered.
HP
Number of hours the motor has been running.
CF
Number of times the pump has turned on and off.
Cr
Number of times the controller has been turned off.
A1
Total number of times the digital input has triggered the
A1
(No Water) alarm has been triggered..
A2
Total number of times the
A2
(Overcurrent) alarm has
been triggered.
A3
Total number of times the
A3
(Open Lead) alarm has
been triggered.
3
Maximum current supplied to the motor (refer to
5 System Description
18
ResiBoost INSTRUCTION MANUAL
Summary of Contents for Goulds ResiBoost RB111512