Parameter name
Level
Description
P0-29:Drive type
2
Displays the type details of the drive: Three entry display: First display
= Frame size and input voltage level. Second display = Power rating.
Third display = Output Phase Count.
P0-30:Serial number
2
Display the unique serial number. Dual entry display: First display =
Serial number (MSB), Second display = Serial number (LMSB).
P0-31:Life run time 1
2
Displays two entries: First display shows hours. Second display shows
minutes and seconds. Displays the total operating time of the drive.
P0-32:Run time since last trip 1
2
Displays two entries: First display shows hours. Second display shows
minutes and seconds. Displays the total operating time of the drive
since the last fault occurred. Run-time clock that stops the drive disable
or trip, reset on next enable only if a trip occurred. Reset also on next
enable after the drive power down.
P0-35:Fan run time
2
Display the total operating time of the drive internal cooling fans.
P0-37:DC bus voltage ripple log
2
Displays the DC bus voltage ripple log. Records the most recent 8
samples of the DC bus voltage ripple before a trip condition. The
sample interval is 20 m.
P0-39:Ambient temperature log
2
Displays the ambient temperature log. Records the most recent 8
samples of the internal ambient temperature before a trip condition.
The sample interval is 30 s.
P0-41:O-I fault counter
2
Displays the number of over current faults.
P0-42:O-Volts fault counter
2
Displays the number of over voltage faults.
P0-44:Heatsink o-temp counter
2
Displays the number of heatsink over temperature faults.
P0-46:Ambient O-temp counter
2
Displays the number of ambient over temperature faults.
P0-50:Alarm log
3
Display the alarm log. Example: Alarm log entry is: AAABC
AAA
Time. 0–600 hours
B
Triggered or reset. 0 = reset, 1 = triggered
C
Alarm code 1–5
1
Pump leakage
2
Pump over temperature
3
High level, Digital level switch
4
Sensor error
5
High level, Analog level sensor
P0-65:Drive life time
3
Displays the time for which the drive has been powered up in hours,
minutes, and seconds since the date of manufacture.
P0-66:PLC program ID
3
Displays the version number of the PLC program.
P0-71:Field bus module ID
3
Displays the fieldbus module identification code.
P0-73:24 hour real timer
3
Displays the value of the internal 24-hour counter, which is displayed
in hours and minutes. This value can be set using the up and down
buttons when the drive is stopped, and is reset to zero on power-up.
P0-74:L1 input voltage
3
Displays the L1 line input voltage.
P0-75:L2 input voltage
3
Displays the L2 line input voltage.
P0-76:L3 input voltage
3
Displays the L3 line input voltage.
P0-79:Control/bootloader version
3
Displays the bootloader version and motor control library version.
P0-80:Specified internal param
3
Displays the version number of the PLC program.
Communication
The drive is equipped with an RJ45 connector. The connection is used to set up a network
via a wired connection. The connector contains two independent RS485 connections and
both can be used simultaneously.
Technical Reference
SRC 311 - SmartRun
™
Installation, Operation, and Maintenance Manual
57