22
500…600 Volt Fuses
500 … 600 Volt
Base
Drive Input Fuse Ratings
Drive
Amps Bussmann
HP Identification Frame
(600V) Type
Size
2
CPC5002xFD
R2
15
KTK-R-15
3
CPC5004xFD
R2
15
KTK-R-15
5
CPC5006xFD
R2
15
KTK-R-15
7.5
CPC5009xFD
R2
15
KTK-R-15
10
CPC5011xFD
R2
30
KTK-R-30
15
CPC5017xFD
R2
30
KTK-R-30
20
CPC5022xFD
R3
50
JJS-50
25
CPC5027xFD
R3
50
JJS-50
30
CPC5032xFD
R4
100
JJS-100
40
CPC5041xFD
R4
100
JJS-100
50
CPC5052xFD
R4
100
JJS-100
60
CPC5062xFD
R4
100
JJS-100
75
CPC5077xFD
R6
125
170M1368
100
CPC5099xFD
R6
125
170M1368
125
CPC5125xFD
R6
160
170M1369
150
CPC5144xFD
R6
200
170M1370
NOTE: “x” represents both NEMA 1 and NEMA 12 enclosures.
Input Power Cables / Wiring – R7/R8
NEC
Based on:
• NEC Table 310-16 for copper wires
• 90 °C (194 °F) wire insulation
• 40 °C (104 °F) ambient temperature
• Not more than three current-carrying conductors in raceway or cable, or earth (directly buried).
• Copper cables with concentric copper shield
Max Load Current (A) Cu Wire Size (AWG/kcmil)
Max Load Current (A) Cu Wire Size (AWG/kcmil)
345
400 MCM or 2 x 2/0
474
2 x 250
391
500 MCM or 2 x 3/0
534
2 x 300
410
2 x 3/0
615
2 x 350
465
2 x 4/0
711
2 x 500
TECHNICAL DATA