background image

8

THREE WAY MIXING VALVES

IMPORTANT:

When  installing  a  three-way  mixing

valve, it is necessary that return circulation be piped to
feed the cold water side of the mixing valve and heater.
See Figure No. 13.

As  the  temperature  of  the  mixed  liquid  increases,  the
piston moves toward the hot seat port B.  See Figure 3
on page 2.  This movement decreases the hot flow and
increases the cold flow through port C. See Figure 3 on
page  2.    The  thermostat  maintains  the  piston  in  the
proper position for the desired mixed temperature.

TO CHECK THE OPERATION OF A THREE-WAY VALVE
USED AS A MIXING VALVE PROCEED AS FOLLOWS:

Check the packing gland to see if it is only hand tight.  If
this gland is too tight, it will bind the valve stem.  Then
open one or two outlets in the hot water line to establish
a flow of water through the valve.  Check temperature on
thermometer.  If it is not at the desired point, increase or
decrease the temperature by turning the adjustment
wheel in the proper direction for a higher or lower
temperature.  The proper direction is indicated by an
arrow on valve bracket.  Two turns of the adjustment
wheel should make an appreciable change in outlet
temperature.

If the temperature at the outlet drops below the desired
point, check the temperature of the hot water entering
the valve.  If it is below the required temperature, the coil
or heater is not making enough hot water.  This condition
must be remedied before any further adjustment can be
made on the three-way valve.

WHEN IN NEED OF INFORMATION

When contacting the factory or one of its representatives
in regard to a regulator, be sure to give all the name
plate Information, fastened to the bellows housing. This
name plate is shown in Figure No. 14.

CIRCULATING PUMP

CHECK

VALVE

REGULATOR

WITH 3 WAY

VALVE

COIL IN
BOILER

PORT

"A"

PORT

"C"

PORT

"B"

COLD BYPASS

HOT BYPASS

BOILER

RETURN CIRCULATION

COLD WATER

SUPPLY

TO BUILDING

Figure No. 13

Figure No. 14

Summary of Contents for Bell & Gossett Hoffman Specialty 1140 Series

Page 1: ...LARMS OR CUT OFFS SHOULD BE INSTALLED ON CRITICAL APPLICATIONS TO INDICATE REGULATOR FAILURE A LEAK COULD CAUSE THE ACTUATOR TO LOSE ITS CHARGE AND CAUSE THE SYSTEM TO OVERHEAT THIS PRODUCT CAN EXPOSE...

Page 2: ...ahead of all steam regulators See Figure No 2 When controlling flow of water used for cooling the valve can be installed on the supply end and may also be installed on the discharge end of the unit Th...

Page 3: ...r as possible When a thermometer is used it should be located PAST the bulb at least 6 ft 1 8 m in the pipeline or on the same level in the tank The bulb can be installed horizontally vertically or in...

Page 4: ...eme temperatures are incurred 2 Form a loop with a few turns of tubing and place next to the regulator This helps to absorb vibra tions in the pipeline SEPARABLE WELL INSTALLATION Separable wells prot...

Page 5: ...stuffing box nut as indicated If valve stem has more travel than indicated valve will not shut off CHANGING VALVE DISC MOVEMENT Under some conditions it may be necessary to adjust the amount of valve...

Page 6: ...s will assist in checking total valve movement on opening and also the thrust of the new thermostatic actuator 6 Cool the new thermostatic actuator bulb which is to be installed at least 20 F 6 C lowe...

Page 7: ...ve spacer and fasten bellows housing in place 9 If stem does not move unscrew upper stem from lower stem a turn at a time until this movement is obtained 10 Stem should move 1 32 0 8 mm Screw upper st...

Page 8: ...t is not at the desired point increase or decrease the temperature by turning the adjustment wheel in the proper direction for a higher or lower temperature The proper direction is indicated by an arr...

Page 9: ...e Capillary has kink Sharp bend will stop signal to pilot Solution Replace actuator or work out kink by hand c Cause Actuator range is incorrect The actuator will not operate beyond its range Solution...

Page 10: ...0 design load at all times h Cause Poor temperature response Solution On units with separable well use high temperature grease between the thermostatic bulb and well for better heat transfer i Cause T...

Page 11: ...11...

Page 12: ...Seller warrants the goods purchased hereunder with the exception of membranes seals gaskets elastomer materials coatings and other wear parts or consumables all of which are not warranted except as o...

Reviews: