36
WET RETURN
SUPPLY MAIN
PACKLESS
RADIATOR
VALVE
REDUCER
CAN BE
REDUCED
(Never Less
than 3/4 ")
NOT LESS
THAN 18"
WATER LINE OF BOILER
VENT
VALVE
DRY RETURN
SUPPLY MAIN
PACKLESS
RADIATOR
VALVE
VENT
VALVE
TRAP
MINIMUM COOLING LEG 5'-0" LONG
RISER
PITCH DOWN FROM HERE
PACKLESS
RADIATOR
VALVE
AIR VALVE
SUPPLY MAIN
PITCH DOWN FROM HERE
PACKLESS
RADIATOR
VALVE
AIR VALVE
Upfeed connection to radiator
Radiator connection taken
from up or downfeed riser
One pipe steam systems radiator connections
Downfeed connections with wet return
Downfeed connections dripping riser into condensation pump return