3  Foundation Requirements

1. Pour grout here up to top surface / plane of base plate

2. Nut

3. Washer

4. Base plate

5. Shims or levelling wedges

6. Bolt sleeve

7. Anchor bolt

8. Concrete foundation

9. Position levelling wedges / shims on both sides of each anchor bolt
Notes:

• Distance from the base plate to the edge of the foundation to be greater than or equal to

1.5”.

• Foundation weight should be greater than or equal to 2.5 times of pump weight.

4  Piping Requirements

1. Check that a section of straight pipe, with a length that is a minimum of five times its di‐

ameter, is installed between the suction side of the pump and the first elbow, or that a

B&G Suction Diffuser is installed.

2. Check that there is a strong, rigid support for the suction and discharge lines.

3. Check that the suction or discharge lines are not forced into position.

4. Check that flexible piping is used on both the suction and discharge sides of the pump

when you use an isolation base.

5. Check that a B&G Triple Duty

®

 valve is installed in the discharge line.

6. Check that the pipeline has isolation valves around the pump and has a drain valve in the

suction pipe.

5  Coupling Alignment

WARNING:

• Follow shaft alignment procedures in order to prevent cata‐

strophic failure of drive components or unintended contact of

rotating parts. Follow the coupling installation and operation

procedures from the coupling manufacturer.

• Always disconnect and lock out power to the driver before

you perform any installation or maintenance tasks. Failure to

disconnect and lock out driver power will result in serious

physical injury.

NOTICE:
Proper alignment is the responsibility of the installer and the user of the unit. Check the align‐

ment of frame-mounted units before you operate the unit. Failure to do so can result in equip‐

ment damage or decreased performance.

6  Checking Rotation

=

1. Lock out power to the driver.

2. Make sure that the coupling hubs are fastened securely to the shafts.

3. Unlock power to the driver.

4. Make sure that everyone is clear, and then jog the driver long enough to determine that

the direction of rotation corresponds to the arrow on the pump.

5. Lock out power to the driver.

For safety and correct product usage, read the manual before this product is used.

2

Summary of Contents for Bell & Gossett e-1510X

Page 1: ...f maintenance tasks Failure to discon nect and lock out driver power will result in serious injury WARNING This product can expose you to chemicals including Lead which is known to the State of Califo...

Page 2: ...line 6 Check that the pipeline has isolation valves around the pump and has a drain valve in the suction pipe 5 Coupling Alignment WARNING Follow shaft alignment procedures in order to prevent cata s...

Page 3: ...7 Electrical installation Figure 1 For safety and correct product usage read the manual before this product is used 3...

Page 4: ...ic GND 10 External lack of water Low water level digital input internal pull up 24 VDC contact current 6 mA 11 Electronic GND 12 Digital input 3 Configurable digital input 3 internal pull up 24 VDC co...

Page 5: ...36 RS485 port 1 RS485 COM 37 Communication Bus 2 RS485 port 2 RS485 2B N Modbus 38 RS485 port 2 RS485 2A P 39 RS485 port 2 RS485 COM 40 Relay 1 Configurable relay 1 normally open Error reporting 41 Co...

Page 6: ...eing established flashing blue Wireless communication and BMS communication active blue alternating green 9 Multifunction button Access the parameter menu or additional functions according to the scre...

Page 7: ...products that are secure by de sign Our customers have a responsibility to understand the risks inherent in their processes and take steps to operate and maintain their solutions securely For details...

Page 8: ...Morton Grove IL 60053 Tel 847 966 3700 Fax 847 965 8379 www xylem com bellgossett Xylem and Bell Gossett are registered trademarks of Xylem Inc or one of its subsidiaries All other trademarks or regis...

Reviews: