• The entrained air is pulled out of solution and forms microbubbles, which coalesce
around the media and form larger bubbles.
• The sediment and dirt particles are strained or filtered from the water and collected in the
bottom of the container.
• The magnetite and other ferromagnetic particles are collected by the optional magnetic
separator.
3.3 Parts
1
2
3
4
WS013376A
1. Skim valve port
2. Air vent, optional
3. Connection to system
4. Blowdown
3.4 Operational limits
Separator
Temperature
Maximum working pressure
CRS
-20°F (-29°C) to 450°F (232°C)
150 psi (1034 kPa)
CRS with magnetic
separation
32°F (0°C) to 250°F (120°C)
150 psi (1034 kPa)