Page | 70
Right click on the Workspace to add the station, select
Create
, then
Instance
, and then the
Ai1
instance. Follow the
steps in section 13.1
” for instructions
on setting Pakbus Address and TCP Callback.
Eagle.io will download the configuration from the Ai1 on
first connection. A connection will be made either on the
measurement interval in the Ai1 or can be manually
triggered. A manual trigger can be initiated through
DevConfig by setting
RenewEagle
(in the public variables
table) to
True
. Once renewed correctly, the Series specific
to the station will be able to be configured through the
Series tab:
-
Set the Location coordinates to Latitude and
Longitude variables using the pulldown icon.
-
Enable the series of interest. The table names are
typically WQ, SondeValues, Level, Weather, IQ, DCS,
Rainfall etc depending on the sensor used. Tick the
Parameters to be stored in Eagle.io. The units are
typically automatically configured from the program
14.4
Alarm Notifications
Once an alarm is configured (i.e., Battery Voltage or Internal Humidity alarms described in section 13.1, or an alarm
from a measurement such as Turbidity), it is possible to subscribe to notifications sent via email
28
.
Subscribe to the parameters or sources
of interest.
When viewing the list of parameters from
a source, click the eye symbol to the right
to change from grey to blue to subscribe.
Enable Notifications on your user profile.
Select your User Profile from the top right
corner and from the Notifications tab,
select the categories of alarms that you
are interested in, for each workspace.
Remember to select only Email unless
SMS costs are included.
Refer to the Eagle.io online documentation (
https://docs.eagle.io/en/latest/topics/alarms/index.html
) for further
information on Alarm Notification.
14.5
Viewing Events
To confirm that a station is updating correctly, it is best to view the low-level events. Select Events from the options
(Map/List/Chart/Events/Dash) in the top right of the window, and then select Debug from the detail level. This will
28
It is possible to subscribe to SMS alarms, but these may be billed for high level usage.