22
6. Specifications
P91-1.5kLi
P91-2kLi
P91-3kLi
1500VA (1350W)
2000VA (1800W)
3000VA (2700W)
15S2P
(15S2P) x 2
(24S1P) x 3
84VDC
17.2 x 15.1 x 3.5***
17.2 x 19 x 3.5***
17.2 x 23.8 x 3.5***
25.6
33.5
45.2
6 ft, 5–15P
6 ft, 5–20P
6 ft, L5–30P
(8) NEMA 5-15R
(8) NEMA 5–15/20R
L5–30R+(6)5–15/20R
Bypass distribution (XBDM), power distribution (XPDU), 4-post rail kit, 2-post shelf kit, wall mount bracket
UL, cUL, RoHS, FCC Class A, battery packs comply to UL1973
2U P91 Li models
*Depending on load level. **Derate capacity to 80% when the output voltage is adjusted to 100VAC. ***Rack depth is front bracket to unit panel. Add 1" for
depth including front bezel.
<=2% THD (linear load), <=4% THD (non-linear load)
55–150VAC* / 50/60Hz auto-sensing
Up to 98%
> 110% & ? 130% for 5 min; > 130% & ?140% for 30 sec; >140% for 1.5 sec
32–104°F (0 ~ 40°C)
11,500 ft above sea level
5 years electronics, 5 years battery warranty (USA and Canada)
RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay/dry contact, Modbus)
ViewPower software, horizontal brackets, tower pedestals, user manual
COMMUNICATION INTERFACE
INCLUDED IN BOX
AVAILABLE OPTIONS
Altitude
APPROVALS
WARRANTY
PHYSICAL
Dimensions (W x D x H, in)
Weight (lbs)
Line cord
Receptacles
ENVIRONMENT
Temperature
BATTERY
Cell Type
LFP26650 2600 mAh
Cell configuration
Charger voltage
52.5VDC
Charger current
1/2/4/6/8A(max.), adjustable through LCD
Recharge time
1.5 hours recover to 90% capacity
Frequency
50/60Hz +/-0.1Hz
Efficiency
Overload capacity
MODEL
CAPACITY
INPUT
OUTPUT
Voltage
100**/110/115/120/127 Vac selectable
Waveform