3-5. UPS Setting
Parameter 1
Parameter 2
There are three parameters to set up the UPS.
P
arameter 1: It’s for program al
ternatives.
Refer to below table.
Parameter 2 is the setting options or values
for each program.
⚫
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 230 Models, You may choose the following output voltage:
200:
presents output voltage is 200Vac
208:
presents output voltage is 208Vac
220:
presents output voltage is 220Vac
230:
presents output voltage is 230Vac (Default)
240:
presents output voltage is 240Vac
For 120 Models, You may choose the following output voltage:
100:
presents output voltage is 100Vac
110:
presents output voltage is 110Vac
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac (Default)
12
5
:
presents output voltage is 12
5
Vac
⚫
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2:
Enable or disable converter mode. You may
choose the following two options:
CF ENA:
converter mode enable
CF DIS:
converter mode disable (Default)
⚫
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
presents output frequency is 50Hz
BAT 60:
presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50:
presents output frequency is 50Hz
CF 60:
presents output frequency is 60Hz