background image

Xtreme Power Conversion Corporation

NXRT-EBP User’s Manual

Page 2

External Battery Packs

Extended Battery Pack User Guide

Estimated Run Time for UPS with Extended Battery Packs

MODEL

LOAD

RUNTIME FOR QTY OF EXTENDED BATTERY PACKS 

IN MIN.

VA

WATTS

UPS

(1) EBP

(2) EBP

NXRT-1000

500

350

23

91

176

1000

700

10

41

80

NXRT-1500

750

525

18

68

124

1500

1050

9

32

60

NXRT-2000

1000

700

29

109

200

2000

1400

14

52

97

NXRT-3000

1500

1050

18

67

123

3000

2100

9

32

60

*For applications requirements of more than two EBP’s, a CBP must be added. See Appendix B for additional 

information.

CAUTION:  It is very critical to connect the correct voltage EBP with the UPS intended.

EBP1 is for NXRT-1000

EBP2 is for NXRT-1500

EBP3 is for NXRT-2000/3000

CONNECTING THE INCORRECT BATTERY PACK TO THE UPS MAY RESULT IN DAMAGE TO THE UPS 

AND/OR BATTERY PACK WILL VOID THE WARRANTY.

All  EBP’s  have  a  different  DC  voltage  configuration  intended  only  for  the  UPS’s  listed  above. 

PLEASE DO NOT MIX EBP’s AND MAKE SURE YOU ONLY CONNECT THE EBP TO LIKE EBP’s OR UPS 

INDICATED ABOVE. DC VOLTAGES ARE MARKED ON BOTH THE UPS AND THE EBP – MAKE SURE 

THEY MATCH. 

Caution label on EBP cable connectors - PLEASE CHECK VOLTAGES CAREFULLY

Summary of Contents for NXRT-EBP

Page 1: ...NXRT EBP External Battery Packs User Installation Manual www xpcc com 2015 Xtreme Power Conversion Corporation All rights reserved Rev 5 20 15 ...

Page 2: ...than two EBP s a CBP must be added See Appendix B for additional information CAUTION It is very critical to connect the correct voltage EBP with the UPS intended EBP1 is for NXRT 1000 EBP2 is for NXRT 1500 EBP3 is for NXRT 2000 3000 CONNECTING THE INCORRECT BATTERY PACK TO THE UPS MAY RESULT IN DAMAGE TO THE UPS AND OR BATTERY PACK WILL VOID THE WARRANTY All EBP s have a different DC voltage confi...

Page 3: ...Xtreme Power Conversion Corporation NXRT EBP User s Manual Page 3 External Battery Packs Extended Battery Pack Configuration EBP1 for NXRT 1000 EBP2 for NXRT 1500 EBP3 for NXRT 2000 3000 ...

Page 4: ...ing EBP s test each EBP to assure proper operation Extended Battery Pack Operation The NXRT UPS System can be connected with up to two EBPs to increase the runtime when connected to the UPS supporting the load 1 The DC Circuit Breaker on the rear of the EBP connects and disconnects the DC bus voltage from the EBP to the UPS The DC Circuit Breaker will also trip to the OFF position in the event of ...

Page 5: ... the EBP connector cover from the UPS rear panel 4 Connect the external DC battery cable from the EBP to the appropriate connector on the UPS 5 Secure the DC battery cable to both the rear of the UPS and the rear of the EBP by using M3 x 8 screws provided 2 each per connector end 6 Repeat the above procedure for testing and securing each additional EBP required 7 Move the DC circuit breaker on the...