Xtreme Power Conversion Corporation
NXRT-EBP User’s Manual
Page 2
External Battery Packs
Extended Battery Pack User Guide
Estimated Run Time for UPS with Extended Battery Packs
MODEL
LOAD
RUNTIME FOR QTY OF EXTENDED BATTERY PACKS
IN MIN.
VA
WATTS
UPS
(1) EBP
(2) EBP
NXRT-1000
500
350
23
91
176
1000
700
10
41
80
NXRT-1500
750
525
18
68
124
1500
1050
9
32
60
NXRT-2000
1000
700
29
109
200
2000
1400
14
52
97
NXRT-3000
1500
1050
18
67
123
3000
2100
9
32
60
*For applications requirements of more than two EBP’s, a CBP must be added. See Appendix B for additional
information.
CAUTION: It is very critical to connect the correct voltage EBP with the UPS intended.
EBP1 is for NXRT-1000
EBP2 is for NXRT-1500
EBP3 is for NXRT-2000/3000
CONNECTING THE INCORRECT BATTERY PACK TO THE UPS MAY RESULT IN DAMAGE TO THE UPS
AND/OR BATTERY PACK WILL VOID THE WARRANTY.
All EBP’s have a different DC voltage configuration intended only for the UPS’s listed above.
PLEASE DO NOT MIX EBP’s AND MAKE SURE YOU ONLY CONNECT THE EBP TO LIKE EBP’s OR UPS
INDICATED ABOVE. DC VOLTAGES ARE MARKED ON BOTH THE UPS AND THE EBP – MAKE SURE
THEY MATCH.
Caution label on EBP cable connectors - PLEASE CHECK VOLTAGES CAREFULLY