Xtreme Power Conversion Corporation
TX90 User’s Manual
Page 12
Uninterruptible Power Supply
UPS Setting
Parameter 1
Parameter 2
Parameter 3
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. There are 6 programs to set up. Refer to below table.
Parameter 2 and Parameter 3 are the setting options or values for each program.
01: Output voltage setting
Interface
Setting
For 208/220/230/240 VAC models, you may choose the fol-
lowing output voltage:(Default 230Vac/120Vac)
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac
For 110/115/120/127 VAC models, you may choose the fol-
lowing output voltage:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac
127: presents output voltage is 127Vac