![Xtreme Power Conversion M90 User & Installation Manual Download Page 19](http://html1.mh-extra.com/html/xtreme-power-conversion/m90/m90_user-and-installation-manual_891018019.webp)
Xtreme Power Conversion Corporation
M90 User’s Manual
Page 19
Uninterruptible Power Supply
UPS
G
To User Safety ground
Inp
ut
1
R
S
T
N
To Main SUPPLY
(Power Cables)
Inp
ut
2
R
S
T
N
O
ut
put
R
S
T
N
To Critical Load
(Power Cables)
BA
T
+
N
-
To External BATTERY
(Power Cables)
UPS Cabinet Wiring
AC source connection
This UPS is for Single input application, connect Input1 to the AC power source and use 3 short wires to connect
Input1 and Input2.
Warning:
These three wires are required for Maintenance Bypass power source.
The sequence of three phase, R, S and T must be connected accordingly. The wrong sequence will alarm a warning
when the UPS is powered. The N must be connected firmly. A warning message will be indicated, if the N is not
connected well.
External Battery Cabinet Connection
Summary of Contents for M90
Page 11: ...Xtreme Power Conversion Corporation M90 User s Manual Page 11 Uninterruptible Power Supply ...
Page 72: ...Xtreme Power Conversion Corporation M90 User s Manual Page 72 Uninterruptible Power Supply ...
Page 73: ...Xtreme Power Conversion Corporation M90 User s Manual Page 73 Uninterruptible Power Supply ...
Page 76: ...Xtreme Power Conversion Corporation M90 User s Manual Page 76 Uninterruptible Power Supply ...
Page 77: ...Xtreme Power Conversion Corporation M90 User s Manual Page 77 Uninterruptible Power Supply ...