Xtralis Power Supplies VPS-215-E & VPS-220-E Installation and Commissioning Instructions

 

 

www.xtralis.com 

Approved Document No. DFU0002150 Rev 3 

www.xtralis.com 

Page 2 of 2 

Legend 

Description (UK) 

Description (FR) 

Beschreibung (DE) 

Descriptiόn (ES) 

Descrizione (IT) 

Value 

 

AC supply 

 

 

 

 

230Vac, 50/60Hz (10% / -15%) 

 

AC supply input terminals 

 

 

 

 

L=LIVE, N=Neutral, 

=Earth 

 

PSU earth strap: connect to enclosure 
earth tag 

 

 

 

 

PSU is CLASS 1 AND MUST BE EARTHED 

 

AC supply fuse (F1): high rupturing 
capacity, ceramic 

 

 

 

 

1A HRC, 20mm 

 

Red LED: 

Hazardous voltages in PCB 

hashed area

 

 

 

 

 

Hazardous voltages =

 

 

 

PLK1 Charge current link. Remove if 
using batteries <7Ah (Minimum 2Ah) 

 

 

 

 

 

PLK2 Battery monitoring link. Fit if 
batteries NOT used 

 

 

 

 

 

 

Power output (maximum and battery cut 
off voltage) 

 

 

 

 

24Vdc (V max = 30V, V min = 19.5V) 

I max a & I max b with PLK1 fitted 

 

 

 

 

0.5A 

I max a & I max b with PLK1 NOT fitted 

 

 

 

 

1A (non EN54-4 certified) 

Output ripple voltage (peak-to-peak) 

 

 

 

 

1.2V@30MHz bandwidth, 600mV 100nF loading 

 

Battery connection to VRLA batteries 

 

 

 

 

 

Maximum internal battery resistance 

 

 

 

 

Ri max = 1500mΩ 

I min: Monitoring current in load shed 

 

 

 

 

<12mA 

AC supply/battery charger monitored 

 

 

 

 

 

Batteries monitored 

 

 

 

 

 

Charging is temperature compensated 

 

 

 

 

 

VPS-215-E battery size (Yuasa NP type 
or equivalent) 

 

 

 

 

2 x 12V, 7Ah (NP7-12) 

VPS-220-E battery size (Yuasa NP type 
or equivalent) 

 

 

 

 

2 x 12V, 7Ah (NP7-12) or  
2 x 12V, 12Ah (NP12-12) or 
4 x 12V, 7Ah (NP7-12) 

 

VPS-215-E indications: Internal only. 
Output OK (Green LED), Fault (Yellow LED) 

 

 

 

 

Output OK = 

     Fault =

 

VPS-220-E indications: External only. 
Output OK (Green LED), Fault (Yellow LED) 

 

 

 

 

Output OK = 

     Fault =

 

 

PL1: 4-way display connector 

 

 

 

 

 

 

Fault relay: isolated relay output 

 

 

 

 

Change-over NO-COM-NC 1A@50V 

 

PL2: high temperature output (unused) 

 

 

 

 

Operates at approx 55

o

C internal box temp, 30V 

200mA max current sink. 

 

Battery fuse (F2): fast, glass 

 

 

 

 

3.15A F, 20mm 

 

Charge Off Input: Disablement of battery 
charger when closed (unused) 

 

 

 

 

 

 

Wiring loom to Display PCB (VPS-220-E 
only) 

 

 

 

 

 

 

VPS-215-E dimensions (H x W x D) 
VPS-215-E weight (without batteries) 

 

 

 

 

286 x 226 x 113mm 
2.5kg 

VPS-220-E dimensions (H x W x D) 
VPS-220-E weight (without batteries) 

 

 

 

 

351 x 255 x 110mm 
3kg 

VPS-215-E mounting 

 

 

 

 

4 x Ø5mm holes on 220 x 180mm centres 

VPS-220-E mounting 

 

 

 

 

4 x Ø5mm holes on 270 x 180mm centres 

Temperature range 
Maximum relative humidity (RH) 
Ingress protection (IP) Rating 

 

 

 

 

-5

o

C to +40

o

C ambient 

95% RH 
IP30 

 

 

 
 
 
 