background image

Xtralis Power Supplies VPS-215-E & VPS-220-E Installation and Commissioning Instructions

 

 

www.xtralis.com 

Approved Document No. DFU0002150 Rev 3 

www.xtralis.com 

Page 1 of 2 

VPS-215-E & VPS-220-E are power supply units (PSU) for Xtralis Aspirating Smoke Detectors (ASD). 
They are compliant with EN54-4:1997+A1:2002+A2:2006. 

Xtralis VPS-215-E 

(0.5A load, 7Ah max) 

and 

Xtralis VPS-220-E 

(0.5A load, 14Ah max) 

 

Location

: Site the PS

U indoors on a dry, flat surface in an area that is well ventilated. Where possible the panel’s indicators (internal and 

external) should be at eye level and the unit should be installed in the same location as the ASD it powers.

 

 

 

Knockouts

: Before mounting, remove selected knockouts with a sharp light tap, using a flat broadsided screwdriver (shown right). Fill knockout 

holes with good quality cable glands.

 

 

 

Mounting

: Mount the metal base securely onto a wall using the four mounting holes provided. Assess the condition and construction of the wall 

and use No.8-10, or 4-5mm screws. Use the fixing hole template overleaf as a guide. 

 

 

Wiring

:  Connect  all  AC  cables  BEFORE  applying power.  Maintain  segregation  between  AC  and  DC  cabling. All  wiring  should  be installed  in 

accordance with relevant national standards, e.g. IEE Wiring Regulations BS7671 in the UK.  Connect the incoming AC to CONN1 

(

② 

shown 

overleaf

)

 and ensure that earth straps are connected to the earth tag (shown right).

 

 

 

 

Connect DC:

 Connect the DC output to the Xtralis detector. Examples for the VESDA VLC, VLP and VLF are shown below which may use the General Purpose Input (GPI) to transmit the PSU 

fault signal. The VESDA detector must be configured to interpret the GPI input as a ‘Mains OK’ if this feature is used.

 

 

 

 

 

Connect Batteries

: Secure the batteries using battery straps and connect as shown. With charged batteries the DC output 

 will turn on, the OK LED will illuminate and the Fault LED will also 

illuminate (as there is no AC input). 

CAUTION: Only use good quality sealed Valve Regulated Lead Acid (VRLA) batteries. There is a risk of explosion if the batteries are replaced by incorrect types. 

 

 

 

 

 

 

Commissioning: 

Switch on the AC supply to the PSU. The OK LED should stay lit and the Fault LED should turn off. 

Check the fault relay is energized 

(

short circuit between C and NO terminals 

)

. Switch off the AC supply and confirm correct 

operation of LEDs and relay 

– see table right. Restore the AC supply. Disconnect the batteries and confirm correct operation of 

LEDs and relay 

– see table right.

 

 

Normal Operation/Fault Finding: 

The table in Step 7 provides a summary of the normal operation of the PSU when the battery and/or AC supply fails. When the AC supply fails, the DC output 

is maintained for at least 24 hours as long as the batteries are in good condition. Damage to the batteries as a result of deep discharge is prevented by turning the DC output off (load shed mode) 
when the battery voltage falls below approximately 21V. Should this happen the DC output will not be restored until the AC supply is re-established OR fully charged batteries have been installed. 
However, the terminal voltage of the discharged batteries measured after the PSU has entered load shed mode may be greater than 21V because the voltage can recover when the battery is not 
under load. Never leave the batteries connected for prolonged periods without an AC supply connected because, during load shed mode, there is a monitoring current Imin (<12mA) which, over 
several days, will drain the batteries to the point they are damaged.

 

AC 

Batteries 

OK 

LED 

Fault 

LED 

Fault 
relay 

Fault terminals 

ON 

OK (Healthy) 

ON 

OFF 

ON 

NO-C=short 

OFF 

ON 

ON 

OFF 

NC-C=short 

ON 

Not OK 

(Discharged or 

Disconnected 

or Faulty) 

ON 

ON 

OFF 

NC-C=short 

OFF 

OFF 

OFF 

OFF 

NC-C=short 

 

Reviews: