VESDA VLI Product Guide
VESDA by Xtralis
26
www.xtralis.com
3.4
Configuration
The VLI detector can be configured using Xtralis VSC software installed on a direct or network
connected PC.
3.4.1
Default Settings
Table 3-3: Default Settings
Parameter
Default Values
Range
Access
Level
Minimum
Maximum
Event Log - Events
l
Smoke Level
Enabled
n/a
n/a
Adm
l
Alarms
Enabled
n/a
n/a
Adm
l
Faults
Enabled
n/a
n/a
Adm
l
User Action
Enabled
n/a
n/a
Adm
Thresholds
l
Alert
0.2% obs/m
(0.064% obs/ft)
0.05% obs/m
(0.016% obs/ft)
1.990% obs/m
(0.637% obs/ft)
Adm
l
Action
(Pre-Alarm)
0.3% obs/m
(0.096% obs/ft)
0.1% obs/m
(0.032% obs/ft)
1.995% obs/m
(0.638% obs/ft)
Adm
l
Fire1
(Alarm)
0.4% obs/m
(0.128% obs/ft)
0.15% obs/m
(0.048% obs/ft)
2.0% obs/m
(0.64% obs/ft)
Adm
l
Fire2
2.0% obs/m
(0.64% obs/ft)
0.155% obs/m
(0.05% obs/ft)
20.0% obs/m
(6.4% obs/ft**)
Adm
Alarm Delays
10 Seconds
0 Seconds
60 Seconds
Adm
Delay Times
Simultaneous
Simultaneous
Cumulative
Adm
Instant Fire
Disabled
Enabled
Disabled
Adm
Change-over Times:
l
Day
l
Night
l
07:00:00
l
19:00:00
Two Seconds
11:59:58
Adm
Weekend
Saturday & Sunday
Adjust to suit
environment
Adjust to suit
environment
Adm
Holidays
l
First Day
l
Last Day
l
1-Jan-90
l
1-Jan-90
Adjust to suit
environment
Adjust to suit
environment
Adm
Smoke Change:
l
Change by:
l
Min. Interval
l
0.02% obs/m
(0.006%obs/ft.)
l
2 seconds
l
0.02% obs/m
(0.006%obs/ft.)
l
2 seconds
l
0.2% obs/m
(0.064%obs/ft.)
l
10 seconds
Adm
AutoLearn
14 days
0 hours
0 minutes
0 days
0 hours
15 minutes
15 days
23 hours
59 minutes
Adm
** In default "UL mode", maximum sensitivity is limited to 4%/ft