![Xtralis VESDA VLC-500 Installation Manual Download Page 35](http://html.mh-extra.com/html/xtralis/vesda-vlc-500/vesda-vlc-500_installation-manual_890645035.webp)
VESDA by Xtralis
VESDA VLC Installation Guide
www.xtralis.com
29
Legend
A
Air Filter Cartridge
B
Filter Screw
Figure 10-2: Air Filter Cartridge
3. Lift out the air filter cartridge (A).
Legend
A
Air Filter Cartridge
Figure 10-3: Air Filter Cartridge Removal
Assembly
1. Insert a new air filter cartridge (A).
2. Tighten filter screw (B).
3. Reset the filter counter by connecting a LCD programmer or a PC with Xtralis VSC software to the
programming socket.
4. Using a LCD programmer (VN version only):
l
Enter your user level and PIN number to Log ON to the detector.
l
Initiate the New Filter command located under the Filter menu.
5. Using a PC only (Applicable to RO version) or Using a PC with a PC-Link HLI (Applicable to VN version
only):
l
Enter your user level and PIN number to Log ON to the detector.
l
Initiate Reset Filter Settings command located under the Device menu.
6. Close up the detector.
10.5
Replacing the Aspirator
Disassembly
1. Remove the four screws (A) securing the termination card.
2. Disconnect the aspirator cable loom from the connector on the aspirator.
3. Gently pull out termination card (B) from interface card (connected behind).