ICAM by Xtralis
ICAM Commissioning Guide
www.xtralis.com
11
Parameters to change the display resolution for obscuration, language or imperial/metric units are found in the
SETUP menu option.
Setting Time and Date
Minimum Access Code Required:
Level 1
The time and date settings can be configured through the TIME DATE menu option. The user will be able to
sequentially change the date, month and year, then the seconds, minutes and hours.
Setting IP Address and Mask
Minimum Access Code Required:
Level 1
To set the IP address and mask, navigate to the WEB menu option. Once logged in at the Level 1 access, the
user will be able to set all the IP configuration details for the detector.
Setting the Modbus Address
Minimum Access Code Required:
Level 1
The Modbus address is set through the CONFIGURE menu option using the ADDRESS parameter. Please
ensure that this address is unique for the connected network.
Setting Air Flows
Minimum Access Code Required:
Level 1
All parameters relating to air flow is set through the CONFIGURE menu option. Some of the key parameters
are:
l
FLOWDEL - Flow Fault Delay (1 to 60 s)
l
FLOWHI / FLOWLO - High and low air flow limits for declaring a Flow Fault (0 to 200%)
l
SETFAN - Fan Speed (3 to 10)
Setting Smoke Thresholds
Minimum Access Code Required:
Level 1
Day and night smoke thresholds, trace and delay settings for each sector can be set through the SECTORS
ALMS menu option. Day start and Night start times are accessed through the CONFIGURE menu option via
the NIGHSTART and NIGHSTOP parameters.
Setting GPI Function
Minimum Access Code Required:
Level 2
The 'remote reset' input can be configured for a reset function or an isolate function. Please refer to the RES-
ISOL parameter in the SETUP menu option to configure this GPI.
Setting Up I/O Modules
The type of I/O module included in the detector must be configured in the SETUP menu option, which has a
minimum access of Level 2.
Other options for setting up particular parameters for a I/O module may be achieved through the CONFIGURE
menu option. The minimum access requirement is Level 1. More detail for specific modules may be found in
the appropriate IFT Product Guide.