VESDA-E VEP-A10-P Product Guide
80
www.xtralis.com
7.5
Replacing the Aspirator
Caution:
Electrostatic discharge (ESD) precautions need to be taken prior to removing the fascia from
the detector. A wrist strap must be connected to the case of the detector (Figure 1-1).
Attention :
Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur. Un bracelet doit être raccordé au panneau du détecteur (Figure 7-7).
Ensure the area surrounding the aspirator is clear of dirt and debris prior to replacement.
Care must be taken during aspirator replacement. The aspirator must be correctly seated; it is essential to
ensure that the gaskets are not damaged or dislodged from the underside of the aspirator.
Remove the Aspirator
1. Turn off the 24V DC power to the detector.
2. Open the front door and remove the front fascia. Refer to Sections 7.2 and 1.1 for further information.
3. Disconnect the aspirator cable (A) (Figure 7-10).
A
Figure 7-10: Disconnect the aspirator cable
4. Remove the six screws holding the aspirator to the detector base (Figure 7-11).
Figure 7-11: Remove aspirator mounting screws
5. Remove the aspirator perpendicular to the detector body (Figure 7-12).
Summary of Contents for VESDA-E VEP-A10-P
Page 2: ......
Page 8: ...VESDA E VEP A10 P Product Guide vi www xtralis com This page is intentionally left blank ...
Page 12: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEP A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 78: ...VESDA E VEP A10 P Product Guide 70 www xtralis com This page is intentionally left blank ...
Page 102: ...VESDA E VEP A10 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A10 P Product Guide 98 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A10 P Product Guide 104 www xtralis com Z zone 55 57 73 99 ...