VESDA-E VEP-A00-P Product Guide
76
www.xtralis.com
7.4
Remove the Fascia
Several maintenance functions require that the fascia be removed from the VEP-A00 detector in order to
perform them.
Caution:
Electrostatic discharge (ESD) precautions need to be taken prior to removing the fascia from
the detector. A wrist strap must be connected to the case of the detector (Figure 7-7).
Attention :
Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur. Un bracelet doit être raccordé au panneau du détecteur (Figure 7-7).
Figure 7-7: Wrist Strap application
Remove the Fascia
1. Turn off the 24V DC power to the detector.
2. Remove the two screws along side the door hinge, as shown below in Figure 7-8.