Chapter 2 Installing and Operating
2
Do not disassemble or exchange assembly parts and electric circuits by unauthorized
personnel! Hazard of possible electric shock! In case of repairing, contact your local distributors
or supporting technicians.
In case of damaged shipment and dent, deformation or distortion of the enclosure, contact
authorized local distributor or personnel.
2.1.2 Installing
Install the equipment on a rigid, nonflammable surface and well-ventilated place. If the
equipment is installed on an unstable surface or floor, abnormal noise may be generated.
Keep enough space between wall and back of the equipment for better ventilation.
The voltage, frequency and current of the power supply must be rated at least the same as those
designated on the name plate of the equipment. The switch board is recommended to be
on the back right side of the equipment and equipped with outlet matching the power plug
of the equipment with protective ground (PE).
For possible wet location conditions, where cycle of evaporating and condensing, overflowing or
spillage may occur and for protection against hazard of possible electric shock, use power
socket with appropriate IP protection and additional residual current circuit breaker (RCD)
with rated breaking capacity!
Power socket, switchboard with circuit breaker or residual current circuit breaker for the
equipment shall be located closest to the equipment with good clearance for easy access,
so that immediate interruption is possible under emergent circumstance.
The humidifier shall be connected to a water mains of stable pressure 1 bar±0.2 bar, and a
pressure regulator shall be used where necessary. When tap water is used, a water softener or
purifier of 10
μ
s/cm or less is mandatory. The flexible tubing or hose between water source
and liquid connection of the equipment shall be fixed and protected from mechanical,
thermal and chemical stresses for performance and safety. For specifications and
requirements for a pump booster, pressure regulator, water softener and purifier, consult
Xtemp or local authorized distributor.
The minimum distance away from the ventilating holes at the back of the equipment to the
wall, furniture or other installations shall be 300mm! The inlets of fresh air and outlets of
exhausting air at the back of the equipment shall be kept clear of any obstacles.
Keep the equipment away from hot-air emitting source, direct sunshine, strong magnetic field
and electric sparks!
Neither contamination of high concentration dust or corrosive gas, nor strong airflow surrounds!