8
5.6
Installation dimensions:
6. Technical Data
6.1 Technical data:
Technical Data
Units
Specification
Voltage / Frequency
V / Hz ~ 220-240V / 50-60 Hz
Max. current consumption
A
0.86
Power consumption - Speeds 1, 2
W
17 -65 Max110
Air flow rate
– min - max
m³/h
Min 30 - 120
Max external Static Pressure
Pa
120
Protection category
IP
X2
ambient temperature
°C
-20 to +40
Dimensions (without ducting) - W x H x D
mm
550 x 240 x 510
Weight of MVHR
Kg
10
Duct connections
mm
125 4xDN125
Condensate drain tube connections
mm
20
Filter class
-
F5
Efficiency of Recuperator
%
88
Weight
Kg
11
6.2 Accessories:
Description
Part
Number
Notes
Air Filter Box
45014AA
Suitable for all Xcell MVHRs.
Only one air filter box is required per MVHR.
Not supplied with filters fitted.
Class F7 Filter
95047AA F7 Filter used in the air filter box only.
Pre Heater Unit
44001AA Only one defrost heater unit is required per MVHR.