Cleaning the heat exchanger
The heat exchanger should be cleaned by a specialist technician as and when required depending on the level of
contamination, but at least every 2 years. Contact details for authorised servicing by Xpelair approved technicians
can be found on the back of this booklet.
Disconnect the MVHR from the mains supply.
Remove the Access Hatch by turning it to the left.
Remove the retaining bracket located in front of the Heat Exchanger by removing the screw.
Carefully pull the Heat Exchanger out forwards, keeping it horizontal to avoid damaging the EPP housing.
Thoroughly rinse the Heat Exchanger with lukewarm water and allow all the water to drain off.
Residual moisture will evaporate when the MVHR is operated.
Carefully insert the cleaned Heat Exchanger, keeping it horizontal to avoid damaging the EPP housing.
Replace the Heat Exchanger retaining bracket and retaining screw.
Replace the Access Hatch.
Switch the mains supply back on.
The MVHR is ready to recommence operation.
10 Malfunctions
Important:
Servicing of the MVHR may only be carried out by a qualified service technician. Contact details for
authorised servicing by Xpelair approved technicians can be found on the back of this booklet.
10.1 Fault locating table
FAULT / MALFUNCTION
CHECK
POSSIBLE CAUSE
Supply air or exhaust air fan does
not work
The mains supply is on and all 3
LEDs on the 3-speed switch are
flashing.
-
External air / supply air fan
defective
-
Exhaust air / outgoing air fan
defective
-
Fan blade catching on inner
EPP housing
-
PCB defective (Xcell 150 QVW
models only)
-
Contact fault on motor lines
Supply air or exhaust air fan does
not work
The mains supply is on and no
LEDs on the 3-speed switch are
flashing.
-
Mains supply interrupted
-
Contact fault
-
Fuse has blown
Air volume flow rate (m
3
/h) in sup-
ply air or exhaust air is too low
LED on the 3-speed switch is flash-
ing - filter service indicated.
-
Filter service period has ex-
pired
No water coming through conden-
sate drain hose
Drops of water on the underside of
the MVHR
-
No water in siphon
-
Condensate water drain
blocked
Noise coming from the MVHR
Fans are noisy
-
Increased air resistance due to
contaminated filters / heat ex-
changer
-
Obstruction in the duct system
-
Room air regulator valves not
open wide enough
-
Fan blade touching inner EPP
housing
This table is subject to technical amendments
Summary of Contents for Xcell 150 QV
Page 8: ...8 5 8 Installation dimensions...
Page 23: ...23 11 Customer Notes to record details of filter recuperator cleaning etc...
Page 24: ...24 Customer Notes continued...
Page 25: ...25 Customer Notes continued...
Page 26: ...26 Maintenance Log Date Action Signature Stamp...
Page 27: ...27 This Xpelair MVHR was purchased from Supplier stamp On ________________________ date...