background image

9.

 

Fasten the back-plate to the wall/ceiling using appropriate fasteners. See figure A. 

10.

 

If using screws, do not over tighten. The fan may also be fixed to a wall tube using the clamping brackets. Tighten 

the screws until the fan is firmly secured to the tube – see figure B. 

 

Wire the electrical connections. 

11.

 

Make sure the mains supply is isolated. Switch off the mains electrical supply and remove fuses. 

12.

 

Feed the cable to the terminal block. Wire the fan as shown in Figure F using the diagram appropriate to the fan 

model. 

13.

 

Connect the cable from the isolating switch to the electrical supply wiring. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Settings. 

 

SPEED SETTING 

The fans are factory set to bathroom speed, but have two speed settings for different applications. Select either kitchen or 

bathroom speed by connecting the jumper between the centre and kitchen or bathroom speed pin on the jumper (see Figure 

E) 

 

CV4S /CV4R– see figures D and E. 

 

The pre-set humidity operation is factory set at approximately 75% Relative Humidity (RH), but can be adjusted 

between 65% and 85% RH by control H. 

 

The over-run timer is factory set at 15 minutes but can be adjusted from 30 seconds to 30 minutes by control T. 

 

The over-run timer also sets the length of time the fan runs when activated by a ‘fast’ increase in humidity.  

 

Turn the controls clockwise to increase RH or time and anti-clockwise to decrease. 

 

Using the fan. 

 

The fan will run continuously at its trickle speed setting as set during the installation procedure. 

 

Automatic mode- The fan automatically adjusts to slow changes in natural humidity levels without operating the 

fan.  If the humidity levels increase at a rate slower than 5% RH in 5 minutes, up to the pre-set humidity level, the 

fan will not be triggered by humidity. This is to prevent nuisance triggering of the fan. If humidity levels increase 

quicker than 5% RH in 5 minutes the fan will increase in speed to an interim boost speed setting. When relative 

humidity drops the fan continues to operate for the adjustable time delay.  When the humidity is above the pre-set 

humidity level the fan will run at a higher speed until the humidity drops below the pre-set value. If humidity levels 

do not drop within 5 minutes the fan will further boost to its maximum speed setting until humidity drops. 

 

External operation-  Use the external boost  switch  (if fitted). When the fan is switched off, the fan continues to 

operate for the adjustable time delay then goes into automatic mode.  

 

All Fans 

Re-fit the front cover/baffle assembly by hooking in the top first, and then swing the cover down to clip into place. 

 

Hour run meter 

All fans incorporate an hour run meter that allows the installer to  measure the actual running time of the fan after 

installation. The meter records continuous power supply on time and displays this via an on-board red LED that always 

flashes to indicate the total number of hours the supply has been on (see fig. G). 

 

 

For fixed wiring circuits the protective fuse for the appliance must not exceed 5A. 

 

 

Summary of Contents for Simply Silent CV Series

Page 1: ... supply is switched off before attempting to make electrical connections or carry out any maintenance or cleaning Please leave this leaflet with the fan for the benefit of the user UK customers If you have any queries before or after installing this product call the Xpelair Technical Hotline 44 0 344 879 3588 or e mail customer services glendimplex com Our engineers are there to help you during no...

Page 2: ...tions and wiring must conform to current IEE Regulations UK local or appropriate regulations other countries All Xpelair Simply Silent TM CV Constant Volume fans have the following features Constant Volume fan that automatically adjusts itself to maintain installed air flow rates Continuous running design suitable for bathroom or kitchen applications Two speed extraction Selectable at installation...

Page 3: ... fixing positions Wall tube quickfix clamps Front Cover Removal Depress Cover Latch with tool remove Cover and Baffle Complete A B C D Minimum 30 seconds Maximum 30 minutes Factory settings Timer 15 minutes RH 75 ...

Page 4: ...d immediately above a cooker hob or eye level grill If installing in a room containing a fuel burning device which has a non balanced flue it is the installer s responsibility to ensure that there is enough replacement air to prevent fumes being drawn down the flue when the fan is operating up to maximum extract Refer to Building Regulations for specific requirements Exhaust air must not be discha...

Page 5: ...e between contacts Preparing the Fan for installation 1 Remove the front cover baffle assembly by depressing the latch on the underside of the cover and pulling off the front cover baffle from the bottom See Figure C Mark the position of the back plate 2 Hold the back plate so that the level line marked on it is orientated horizontally 3 Carefully insert the fan tube into the wall duct 4 Mark on t...

Page 6: ...nuously at its trickle speed setting as set during the installation procedure Automatic mode The fan automatically adjusts to slow changes in natural humidity levels without operating the fan If the humidity levels increase at a rate slower than 5 RH in 5 minutes up to the pre set humidity level the fan will not be triggered by humidity This is to prevent nuisance triggering of the fan If humidity...

Page 7: ...ff Repeat 24355 hours total on time 2s off 2s on 0 5s off 2s on 0 5s off 0 5s on 0 5s off 0 5s on 0 5s off 0 5s on 0 5s off 0 5s on 0 5s off Repeat Cleaning recommended once a month 1 Before cleaning isolate the fan completely from the mains supply 2 Remove the front cover baffle plate by rotating the baffle anti clockwise and pulling away from the fan and duct 3 To clean the front cover baffle pl...

Page 8: ...lair or its authorised dealers Caused by repairs or alterations to your Xpelair product not carried out by Xpelair service personnel or its authorised dealer s Caused by use of any consumables or spare parts for your Xpelair product which are not Xpelair specified Terms and Conditions The Xpelair Warranty is valid for Xpelair from the date of purchase of your Xpelair product from a recognised reta...

Reviews: