background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

Installation 

 

If wall mounting the fan, you will also need: 

 

A 100mm diameter prepared hole. 

 

An appropriate external Wall Grille and Ø100mm wall sleeve duct. Kit Ref 91232AW. 

 

Where to locate the fan. 

 

Locate it as high as possible. 

 

At least 110mm from the edges of the mounting surface to the centre of the hole. 

 

As far away as possible from and opposite to the main source of air replacement to ensure airflow 

across the room (e.g. opposite the internal doorway). 

 

Near the source of steam or odours. 

 

 

 

Not where ambient temperatures are likely to exceed 50°C. 

 

If installed in a kitchen fans must NOT be mounted immediately above a cooker hob, or eye level grill. 

 

If installing in a room containing a fuel burning device which has a non-balanced flue, it is the installer's 

responsibility to ensure that there is enough replacement air to prevent fumes being drawn down the flue 

when the fan is operating up to maximum extract. Refer to Building Regulations for specific requirements. 

 

Exhaust air must not be discharged into a flue used for exhausting of fumes from appliances supplied with 

energy other than electric. Requirements of all authorities concerned must be observed for exhaust air 

discharge and intake flow rates. 

 

Not suitable for use in possible chemical corrosive atmospheres. 

 

 

What the installer will need. 

 

3mm electrician’s screwdriver and No.1 or 2 Pozidrive screwdrivers. 

 

 

Wiring and setting up 

Summary of Contents for Simply Silent CV Series

Page 1: ... supply is switched off before attempting to make electrical connections or carry out any maintenance or cleaning Please leave this leaflet with the fan for the benefit of the user UK customers If you have any queries before or after installing this product call the Xpelair Technical Hotline 44 0 344 879 3588 or e mail customer services glendimplex com Our engineers are there to help you during no...

Page 2: ...tions and wiring must conform to current IEE Regulations UK local or appropriate regulations other countries All Xpelair Simply Silent TM CV Constant Volume fans have the following features Constant Volume fan that automatically adjusts itself to maintain installed air flow rates Continuous running design suitable for bathroom or kitchen applications Two speed extraction Selectable at installation...

Page 3: ... fixing positions Wall tube quickfix clamps Front Cover Removal Depress Cover Latch with tool remove Cover and Baffle Complete A B C D Minimum 30 seconds Maximum 30 minutes Factory settings Timer 15 minutes RH 75 ...

Page 4: ...d immediately above a cooker hob or eye level grill If installing in a room containing a fuel burning device which has a non balanced flue it is the installer s responsibility to ensure that there is enough replacement air to prevent fumes being drawn down the flue when the fan is operating up to maximum extract Refer to Building Regulations for specific requirements Exhaust air must not be discha...

Page 5: ...e between contacts Preparing the Fan for installation 1 Remove the front cover baffle assembly by depressing the latch on the underside of the cover and pulling off the front cover baffle from the bottom See Figure C Mark the position of the back plate 2 Hold the back plate so that the level line marked on it is orientated horizontally 3 Carefully insert the fan tube into the wall duct 4 Mark on t...

Page 6: ...nuously at its trickle speed setting as set during the installation procedure Automatic mode The fan automatically adjusts to slow changes in natural humidity levels without operating the fan If the humidity levels increase at a rate slower than 5 RH in 5 minutes up to the pre set humidity level the fan will not be triggered by humidity This is to prevent nuisance triggering of the fan If humidity...

Page 7: ...ff Repeat 24355 hours total on time 2s off 2s on 0 5s off 2s on 0 5s off 0 5s on 0 5s off 0 5s on 0 5s off 0 5s on 0 5s off 0 5s on 0 5s off Repeat Cleaning recommended once a month 1 Before cleaning isolate the fan completely from the mains supply 2 Remove the front cover baffle plate by rotating the baffle anti clockwise and pulling away from the fan and duct 3 To clean the front cover baffle pl...

Page 8: ...lair or its authorised dealers Caused by repairs or alterations to your Xpelair product not carried out by Xpelair service personnel or its authorised dealer s Caused by use of any consumables or spare parts for your Xpelair product which are not Xpelair specified Terms and Conditions The Xpelair Warranty is valid for Xpelair from the date of purchase of your Xpelair product from a recognised reta...

Reviews: