Section 2 – Control
2.4.2 Adjust User Settings :
Use the and keys to select, then press
OK
Fig. 2.7 User Menu : Adjust User Settings
Option : “Filter Change Time” : Select then press OK
Use this to adjust how long the fans run before the filters need to be changed.
Press
OK
to show “Set Filter time”. (Pre-set value is “6 months”). Use the OK and or buttons to select a
new filter time. (Adjustable 2 to 12 months).
Press
OK
to select the option required.
At the end of the Filter time the Display will show
•
“
Replace Filters
” and the unit will continue to run as normal.
•
Press “
OK
” to show “
Filters replaced?
”. Use the
OK
and or buttons to select “
Yes
” or “
No
”
“
Yes
” removes the Filter message and restarts the Filter time. The Display returns to normal.
“
No
” returns to the “Replace Filters” Display.
NOTE!
The filter interval is not reset through power failures or when the unit is switched off.
Option : “Setup Summer Bypass” : Select then press OK
The heat recovery feature is automatically turned off in the summer months by the opening of a “summer
bypass” shutter inside the unit. When the summer bypass is open, the cooler outside air is supplied directly
into the property without being heated up by the extracted warm air.
Press
OK
to show “
Bypass Enable
”. Press
OK
and or buttons to Select “
On
” or “
Off
” – Default is On.
Use or and
OK
buttons to Change and Select :
•
The “
Bypass Start
” Month, when the Bypass feature will begin – Default is April (from 1
st
of the month).
•
The “
Bypass Stop
” Month, when the Bypass feature will end – Default is October (to end of the month).
•
The “
Bypass Temp.
” is the Room temperature above which the Bypass will operate –
Default is 21°C
.
During the set months period, the Bypass will open (“
B
” shows) when the following exists :
•
The temperature
Inside
the property is
1°C above
the Bypass Temp and
•
The temperature
Outside
the property is
1°C below
the Bypass Temp
8