INDEX
USER MANUAL - OPTIMA T09W 6K/10K
www.xmart-ups.com
VER.1801.25-WP+ (ENG)
21
06
NOT USED IN THIS MODEL
07
NOT USED IN THIS MODEL
08
BYPASS
–
ENABLE / DISABLE:
PAR 02: OPN: Allowed: according to PAR 03.
FBD: Prohibited: BYPASS not allowed under any condition
PAR 03: ENA: Enable: Bypass allowed in both manual and automatic.
DIS: Disable: Automatic Bypass allowed but manual is prohibited
Set values with keys:
&
09
MAXIMUM RUNTIME:
This function sets maximum time in Battery mode.
000 a 999: Max. Time in minutes.
DIS: Disable. Runtime will be limited by Battery charge level only.
Set values with keys:
&
10
NOT USED IN THIS MODEL
11
NOT USED IN THIS MODEL
12
NOT USED IN THIS MODEL
13
BATTERY VOLTAGE ADJUSTMENT:
** NO MODIFICATIONS RECOMMENDED
–
ONLY BY TECHNICIANS **
Battery voltage can be adjusted
ADD: for increasing
SUB: for decreasing
Set values with keys:
&