14.- If AC output voltages are similar (lower than 3Vac), please set to "ON" external output breakers for all UPS progressively. Start with UPS
Nº 1, then UPS Nº 2, etc. After that, all UPS outputs are connected in parallel.
15. Check to confirm there are no error or alarm messages on LCDs. At this moment all UPS are working in NORMAL Online mode and
connected in parallel.
16.- It is time to power on equipments connected to UPS output. Power on progressively one by one. Check on UPS LCDs how power output
rises meanwhile equipments are powered on.
** Once all output load is connected check power output is below 100%.
** At this moment, UPS parallel system is powering your system in NORMAL Online mode.