Operation of Xintex Gasoline Fume Detector(s) 
 
There are 3 LEDs located on the Display Unit for each channel on the system, as well as an LED for 
the Blower status.  The Green LED, located at the top, indicates that the system is operational.  
The Yellow LED, located in the center, indicates that there is a Fault in the system.  This is to notify 
the user to check the connections and wire runs of the sensors.  There may be a break in the 
wiring or a disconnected sensor on that channel.  The Red LED, located at the bottom, indicates a 
fume buildup of 20% of the LEL (Lower Explosive Limit) which is considered an alarm.  The Blower 
status LED and alarm horn will actuate when the Red LED is illuminated.  Whenever the Blower 
status LED is illuminated, the Blower is active. 

 
The alarm status will continue as long as the fume level remains at an elevated level.  The alarm 
horn may be silenced by 

pressing the “Check/Reset” button

, but the Blower will remain active 

until the alarm status has ended.  The alarm will reactivate after 30 seconds as long as the 
Detector remains in alarm status.  The problem should never be considered corrected as long as 
the Red LED is illuminated.   
 
 
 
 
 
 
 
 
 
 
 

G1BR-B01-D 
G1CR-B01-D 
 

G2BS-B01-D 

Summary of Contents for G-1BB-24-R

Page 1: ...24V Solenoid G 1CB R Chrome Round Blower Control 12V Solenoid G 1CB 24 R Chrome Round Blower Control 24V Solenoid Dual Channel System G 2BB R Black Square Blower Control 12V Solenoid G 2BB 24 R Black...

Page 2: ...4 Installation 6 Installing the Display Unit G1BR B01 D G1CR B01 D or G2BS B01 D 6 Routing Sensor Cable s FS X01 CABLE XX 6 Installing Gasoline Fume Sensor s FS T01 6 Electrical Connections G1BR B01...

Page 3: ...tem Specifications G 1BB R G 1CB R Operating Voltage 9 30V DC Nominal Current Draw 55mA 12V DC Maximum Current Draw 95mA 9V DC Maximum Blower Output Current 2A Operating Temperature 40 F 40 C to 185 F...

Page 4: ...The Red LED located at the bottom indicates a fume buildup of 20 of the LEL Lower Explosive Limit which is considered an alarm The Blower status LED and alarm horn will actuate when the Red LED is il...

Page 5: ...Switch YELLOW Switching Ground 2A Fuse Included Positive voltage from Blower Circuit Breaker MB30RLY 30 85 87 86 G1BR B01 D G1CR B01 D FS X01 CABLE XX FS T01 RED Power 1 0 Amp Fuse from Circuit Break...

Page 6: ...of the Gasoline Fume Sensor Connect to the Display Unit using the attached quick disconnect connectors Take care not to pinch break or cut the Sensor Cable or put too much stress on the connectors whi...

Page 7: ...e Detectors can be tested by pressing the Check Reset button on the face of the Display Unit The Display Unit will cycle through the LEDs and the alarm horn will activate while the LEDs cycle Unplug t...

Page 8: ...and make any necessary repairs Repairing Xintex Gasoline Fume Detection Components Xintex Gasoline Fume Detection Components are not field serviceable Components must be returned to the factory for a...

Page 9: ...ent of Fireboy Xintex LLC does not assume the costs of removal and or installation of the product or any other incidental costs of removal and or installation of the product or any other incidental co...

Reviews: