Extension ED module
XD-2AD2DA-A-ED
Fast manual
Thanks for purchasing XINJE XD series PLC and extension module. This manual will
introduce the electric features and using method of XD series extension ED module. Please
read this manual carefully before using the products, make sure the wiring operation is safe.
Features of analog extension module
XD-2AD2DA-A-ED
2 channels analog input: current input mode, 0~20mA or 4~20mA.
2 channels analog output: current output mode, 0~20mA or 4~20mA.
12-bit high precision analog input, 10-bit high precision analog output.
As the special function ED module of XD, XD series PLC can connect 1 XD-
2AD2DA-A-ED module.
Safety precautions
Control system design attentions
Dangerous!
Make sure design the safety circuit, to ensure that the control system can still work
safety when the external power supply cut off or PLC broken.
Make sure set emergency braking circuit, protection circuit, interlock circuit of forward-
reverse running in PLC external circuit and upper-lower limit switch to prevent from
machine damage.
In order to make the equipment safe operation, please design external protection circuit
for important output signal.
PLC CPU will close all the output when detecting the system error; the output will lose
control when the PLC circuit has problem. Please design suitable external control circuit
to ensure the device working normally.
If the PLC relay or transistor unit is broken, the output cannot be ON or OFF.
The PLC is designed for indoor environment, the lightning protection must be installed
in the power supply system to avoid PLC and other device damage.
Installation and wiring attentions
Dangerous!
Do not use the PLC in the following environment: dust, soot, corrosive gases,
flammable gas, high temperature, condensation, vibration, impact, lightning, fire.
Do not let the metal scrap and wire head drop into the ventilation hole of PLC, otherwise
it will cause fire or error operation.
Do not cover the ventilation hole of PLC, otherwise it will cause fire, error operation.
The I/O wiring must be fixed enough, otherwise the bad contactor will cause fault.
Attention!
It can use external power supply for extension module DC24V power.
Please use shield cable for high frequency I/O wiring to avoid interference.
Run and maintenance
Dangerous!
Please connect all the cable include PLC, extension module and BD board after shutting
down the power supply.
Please operate as the manual for online operation, forced output, RUN, STOP.
Attention!
Please discard the product as industrial waste.
Make sure cut off the power supply when installing or uninstalling the extension card.
Product information
Naming rule
XD– 2 AD 2 DA - A - ED
①
②
③
④
⑤
⑥
⑦
①
Product series XD: XD series extension module
②
Analog input channel: 2: 2 channels
③
Analog input AD: analog input
④
Analog output channel: 2: 2 channels
⑤
Analog output DA: analog output
⑥
I/O type A: current type for input and output
⑦
Module type ED: left extension ED module
Basic parameters
XD series PLC can connect 1 extension ED module, the type is not limited.
Table 1: analog extension module XD-2AD2DA-A-ED general specifications
Item
Specifications
Using environment
No corrosive gas
Environment temperature
0
℃
~60
℃
Storage temperature
-20~70
℃
Environment humidity
5~95%RH
Storage humidity
5~95%RH
Installation
Fix with M3 screw or install on the rail DIN46277(width
35mm)
的导轨上
Dimension
100.0mm×18.0mm×90.0mm
Table 2: analog extension module XD-2AD2DA-A-ED I/O precision
Item
Analog current input (mA)
Analog current output (mA)
Analog input
range
0~20, 4~20mA
—
Max input range
0~40mA
—
Analog output
range
—
0~20, 4~20mA
External load resistor is less than
500Ω
Digital input
range
—
10-bit binary number (0~1023)
Digital output
range
12-bit binary number
(0~4095)
-
Resolution
1/4095(12Bit)
1/1023(10Bit)
integrated
precision
1%
Transformation
speed
2ms/1 channel
2ms/1 channel
Power supply for
analog
DC24V±10%, 150mA
Table 3: analog extension module XD-2AD2DA-A-ED AD transformation diagram
The relationship between analog input and transformed digital value
0~20mA analog input
4~20mA analog input
20mA
+4095
0
analog
di
gi
t
al
20mA
4mA
+4095
0
analog
di
gi
t
al
The relationship between analog output and digital input
0~20mA analog output
4~20mA analog output
20mA
+1023
0
an
al
o
g
digital
20mA
4mA
+1023
0
an
al
o
g
digital
Note: when the input data is over K1023, DA transformed analog output will keep 20mA.
Product appearance
Here listed I/O terminal configurations of XD series extension module XD-2AD2DA-A-ED.
Product structure
Each part name:
Name
Function
Indicator
light
PWR
The LED lights when the ED module has power supply
COM
The LED lights when the ED module communication
port works well
ERR
The LED lights when the ED module has error
Wiring
terminal
24V
ED module external power supply 24V +
0V
ED module external power supply 24V -
AI0
Channel 1 analog input
AI1
Channel 2 analog input
CI0
AI0, AI1 ground
AO0
Channel 1 analog output
AO1
Channel 2 analog output
CO0
AO0, AO1 ground
Product dimension and installation
Installation
Do not install the module in below environment:
Direct sunlight
Environment temperature out of range 0-50
℃
Environment humidity out of range 35%-85% RH
Condensation as severe changes in temperature
Corrosive gas and flammable gas
Dust, iron filing, salt, fume
Vibration and impact
Spray oil, water and medicine
Strong magnetic field and strong electric field
XD series extension ED module can be installed in com3 port of XD series PLC.
Note: please cut off the power before operation!
Product dimension
(Unit: mm)
XD series extension ED module dimension is shown as below:
Electric design reference
I/O address
XD series extension ED module will not occupy I/O unit, the transformed value is stored in
PLC register. The following is the PLC register corresponding to each channel.
Channel
AD signal
0CH
ID30000
1CH
ID30001
Channel
DA signal
0CH
QD30000
1CH
QD30001
Working mode setting
TYPE:XDM-32T4-E
DATE:20120701
SN:201207011525
Xinje Electronic Co.,Ltd
COM3
PWR
COM
ERR